4
MOUNT CENTER OFJUNCTION BOX
22 3/8” (568mm) TO THE RIGHT OF CENTER OF STUD
PERMANENT 120V ac
FROM HOUSE POWER
22 3/8”
(568mm)
16” (406mm)
15 1/4”
(388mm)
8 1/8”
(206mm)
1/2” (13mm) CONDUIT
Hardwired Model Only
2” x 4”
(51mm x 102mm)
ELECTRICAL BOX
FOR TIMER
Hardwired Model Only
2” x 4”
(51mm x 102mm)
ELECTRICAL BOX FOR TOWEL
WARMER CONNECTION
†
2” X 4” STUD
(51mm x 102mm)
2” X 4” STUD
(51mm x 102mm)
1. Affixing the Towel Warmer to the Wall
(continued)
Diagram B: Rough-In Diagram
Note:
Dimensions shown are distances between the center of anchor
points. This example shows 16 inches on center construction. Your
situation may vary depending on stud spacing.
WARNING:
Locations of electrical box and anchor points may vary.
Measure all dimensions prior to rough-in and installation.
†
Note: For hardwired model only, electrical box must be securely attached to a
stud. Plug-in model only must be installed less than 6 feet (183cm) from
properly grounded outlet. Do NOT use an extension cord.
* Note: Anchor points must be attached to a stud.