PELLET STOVES                                                23                                                                 PS45B   041113-24

MODEL    

PS45

Series A               

CLASSIC

                                                        PED.

 

 

 

 

               

LEG

TESTED TO/ TESTÉ SELON LA NORME: ASTM E 1509-04 / ULC S627-00

  INPUT / PUISSANCE : 12,000 - 45,000  Btu/Hr    ELECTRICAL/ELECTRIQUE: 120V A/C, 4.3AMP, 60Hz

  Install and use only in accordance with pacifi c energy installation and operating instructions.
•  Contact local building or fi re offi cials about restrictions, permits and inspection in your area.  
•  Use only, 3" or 4" "PL" or "L" listed exhaust venting systems.  Inspect and clean exhaust venting system frequently.
•  DO NOT connect this unit to a chimney fl ue serving another appliance 
• S

ee local building code and pacifi c energy instructions, as well as vent manufacturer's  instructions for precautions 

required when passing exhaust venting through a combustible wall or ceiling.

• For use with only wood pellet fuel. DO NOT USE OTHER TYPES OF FUEL.
•  WARNING: FOR MOBILE/MANUFACTURED HOMES: Do not install appliance in a sleeping room.  Unit must be con-

nected to outside air.  Structural integrity of the home fl oor walls and ceiling must be maintained.

• Keep viewing door and ash drawer closed tightly during operation.
•  DO NOT obstruct air openings.   

Replace glass only with 5mm ceramic glass from your dealer.

Keep furnishings and other combustible materials well away from heater.

  Use only components specifi ed in the PS45 installation instructions. 

  REQUIRED PARTS: DR31 DOOR.  

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS (measured from sides of unit)

  COMBUSTIBLE FLOOR MUST BE PROTECTED BY A CONTINUOUS NON-COMBUSTIBLE MATERIAL EXTENDED PAST 

THE FRONT (E) 6 in/155 mm, SIDES (F) 3 in/75 mm AND BACK UNDER VENT TEE IF INSTALLED.

  ALCOVE SIZE : Maximum DEPTH - 24 in. / 0.61m.  -  Minimum HEIGHT 5 FT. / 1.52m

TOUT PLANCHER EN MATÉRIAUX COMBUSTIBLES DOIT ÊTRE PROTÉGÉ PAR UN PLATE-FORME CONTINUE EN 
MATÉRIAUX NON COMBUSTIBLES DÉPASSANT À L’AVANT (E) 6 in./ 155 mm, AUX CÔTÉS (F) 3 in./ 75 mm ET À 
L’ARRIÈRE DU POÊLE TEL QU’INDIQUÉ.

DIMENSIONS POUR INSTALLATION DANS UNE ALCÔVE : Maximum PROFONDEUR : 24 po. / 0,61m.  - 
   

                       Minimale HAUTEUR : 5 PIEDS / 1,52m.

•   Installez et utilisez selon les instructions d’installation et d’utilisation de pacifi c energy.  
•   Contactez les agents locaux du bâtiment ou du service-incendie concernant les restrictions, le permis d’installation et 

les exigences d’inspection applicables à votre région. 

•  Utilisez seulement 3" ou 4" conduits d’évacuation homologués de type "PL" "L"
•   Inspectez et nettoyez fréquemment le conduit d’évacuation.
•   Ne raccordez pas cet appareil à un conduit de cheminée desservant un autre appareil.
•   Si le conduit d’évacuation traverse un mur ou plafond en matériau combustible voir les exigences du code du bâtiment 

local et celles de pacifi c energy et du fabricant de conduit d’évacuation

•   Pour utilisation seulement avec des granules de bois.  N'obstruez pas les ouvertures d'air
•   La porte vitrée et le tiroir à cendres doivent être tenus bien fermés durant le fonctionnement.
•   Appareil de chauffage ambiant à combustible granulé, conçu aussi pour les maisons mobiles.
•   Tenez les meubles et autres matériaux combustibles à une bonne distance du poêle.
•  Utilisez seulement les composants spécifi és dans les instructions d’installation de PS45.
•   La vitre doit être remplacée seulement par une vitre en 5mm céramique.
•  PIÈCES EXIGÉES : PORTE DR31

MADE IN CANADA

CERTIFIED FOR CANADA AND U.S.A./ CERTIFIÉ AU CANADA ET 
AUX ÉTATS-UNIS.
LISTED ROOM HEATER,/ APPAREIL DE CHAUFFAGE AMBIANT
PELLET FUEL-BURNING TYPE./ HOMOLOGUÉ, DE TYPE À 
GRANULES.
ALSO FOR USE IN MOBILE HOMES/ CONÇU AUSSI POUR 
MAISONS MOBILES

191011         

 5050.831 

PS45-1

A.  SIDEWALL TO UNIT            6 in.(po.) / 152 mm 
    

MUR LATÉRAL AU POÊLE

B.  BACKWALL TO UNIT          3 in.(po.) / 76 mm 
    

MUR ARRIÈRE AU POÊLE

C.  CORNER TO UNIT              3 in.(po.) / 76 mm
    

DU COIN AU POÊLE

D.  BACKWALL TO VENT.        3 in.(po.) / 76 mm **

**SEE VENT MANUFACTURES SPECIFICATIONS 

            **VOYEZ QUE LE PASSAGE FABRIQUE DES CARACTÉRISTIQUES 

DO NOT REMOVE THIS LABEL/ NE RETIREZ PAS CETTE ÉTIQUETTE.

J   F   M   A   M   J   J   A   S   O   N   D

  2010   2011    2012    2013    2014    2015

DATE OF MANUFACTURE/ DATE DE FABRICATION

C

B

A

F

E

D

BACKWALL

SIDE

W

ALL

DÉGAGEMENTS MINIMUMS AUX MATÉRIAUX COMBUSTIBLES

MANUFACTURED BY/FABRIQUÉ PAR :

PACIFIC ENERGYFIREPLACE PRODUCTS LTD.

2975 ALLENBY RD., DUNCAN, BC  V9L 6v

8

WN#16593                      ETL#4001507

U.S. ENVIRONMENTAL PROTECTION AGENCY

This model is exempt from EPA certifi cation under 40 CFR 

60.531 by defi nition [Wood Heater (A) "Air-to-Fuel Ratio"].

MINISTÈRE DE L'ENVIRONNEMENT U.S.

Ce modèle est exempt de la certifi cation de MINISTÈRE 

DE L'ENVIRONNEMENT sous 40 CFR 60.531 par défi nition 

[l'Appareil de chauffage En bois (A) "la Proportion 

Aérienne-à-carburant"].

Rating Label

Summary of Contents for PS45 series A

Page 1: ...ED to ASTM 1509 04 CAN ULC S627 AND UL 1482 IMPORTANT THESE INSTRUCTIONS ARE TO REMAIN WITH THE HOMEOWNER SAVE THESE INSTRUCTIONS MODEL PS45 SERIES A Wood Energy Technical Training www wettinc ca SAFE...

Page 2: ...Air 10 Thermostat installation 12 Operation 12 Filling the Hopper 12 Control Board 12 Fault Codes 12 General Operation 13 Thermostat Operation 13 MANUAL Mode 13 Paint Curing 13 Plated Surfaces 13 Rout...

Page 3: ...detectors Ifyourlocalcoderequiresasmokedetectorbe installedwithinthesameroom youmustfollowtherequirements ofyourlocalcode Checkwithyourlocalbuilding firedepartment for requirements in your area THERMO...

Page 4: ...Pressure Warning This appliance has not been designed to be operated in a negatively pressurized room Provide adequate air for combustion The stove s exhaust system works with negative combustion cham...

Page 5: ...ape the clinkers out Clean the holes with a small pointed object if required Refer to the section Routine Cleaning and Maintenance Wood Pellet Specifications This appliance has been designed to burn w...

Page 6: ...meets local building codes It is recommended that the unit be secured into its position in order to avoid any displacement Thisappliancemustbeinstalledonafloorwithan adequate load bearing capacity if...

Page 7: ...rances removal of the appliance may be necessary for servicing Recommended clearance zone from the front of the appliance to combustibles is 4 feet minimum NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE...

Page 8: ...m from the edge of the terminal E 12 inches 30 cm Clearance to unventilated soffit F 12 inches 30 cm Clearance to outside corner G 12 inches 30 cm Clearance to inside corner H 3 feet 90 cm Not to be i...

Page 9: ...oke or odor during appliance shut down or power failure and avoid exposing people or landscaping shrubs to high temperatures Hooded vent Using existing wood vent Thru roof Recommended Recommended Reco...

Page 10: ...without any vertical sections of pipe are approved however it is recommended that a minimum of 5 ft of vertical be included in the vent system Having a vertical section in the venting will help preven...

Page 11: ...safely all sections of listed connector offset elbows and chimney section must be screwed to gether by at least three sheet metal screws per joint The chimney must be suitably supported by the chimney...

Page 12: ...n requirements If the location requirements are not followed the appliance may operate erratically or failure may occur Do not mount the thermostat where it may be affected by Radiant heat from the st...

Page 13: ...stove has run out of pellets the auger will be empty and the Burn Pot liner will need to be primed To prime place a handful of pellets into the middle of the liner On the control board push the ON OFF...

Page 14: ...ppliance A cleaning brush can be used to loosen any ash build up before vacuuming DONOTUSEASTANDARDHOUSEHOLDVACUUM WHEN USINGA SHOPVACUUM A FINE DUST FILTER MUST BE INSTALLED AS THE STANDARD FILTERS W...

Page 15: ...stove Vacuum out the Ash Pan enclosure before inserting the Ash Pan Fig 13 CAUTION Disposal of Ashes Ashes should be placed in a metal container with a tight fitting lid The closed container shouldbe...

Page 16: ...n the exhaust passages fig 18 Fig 18 Don tforgettocleanuparoundtheheatexchanger Oncetheflue passage is clear of ash build up reinstall the Firebox Liner Firebox Passage Clean through here Cleaning the...

Page 17: ...crews Cleaning the Convection Blower To clean the convection blower remove the right cabinet side see previous page Disconnect the stove power cord from the electrical outlet Using a 3 8 wrench remove...

Page 18: ...and shuts the stove down if it senses excessive temperatures Opens at 200 F This snap switch has a reset button on it and will not allow the stove to start up until the reset button has been pushed P...

Page 19: ...PELLET STOVES 19 PS45B 041113 24 Wiring Diagram 5050 838 A 010210 PS 45 WIRING...

Page 20: ...5024 504 FASCO 7073 1918 21 1 5027 175 HOPPER SWITCH 22 1 5001 004 400W IGNITOR 23 1 5027 173 Pellet Vacuum Switch 24 1 5001 001 AUGER ASSEMBLY D 1 PSRP 7384 VENT STARTER TUBE ASSEMBLY 25 1 5068 7173...

Page 21: ...PELLET STOVES 21 PS45B 041113 24 a b C D...

Page 22: ...PELLET STOVES 22 PS45B 041113 24 a b a b A B...

Page 23: ...vice incendie concernant les restrictions le permis d installation et les exigences d inspection applicables votre r gion Utilisez seulement 3 ou 4 conduits d vacuation homologu s de type PL L Inspect...

Page 24: ...PACIFIC ENERGY FIREPLACE PRODUCTS LTD www pacificenergy net 2975 Allenby Rd Duncan BC V9L 6V8 Phone 250 748 1184...

Reviews: