background image

23 November 2016

 

Due to continued product improvement, Warmington Ind LTD reserves the right to change product specifications without prior notification.

 

All Dimension are in mm………….Copyright © 

 

6

 

PLAN, FRONT ELEVATION & CROSS SECTION 

 

TIMBER FRAMING & TRIM OUT DETAILS

-

Heat Cell Clearance

 

Note:

 

Centre line of flue is `NOT’ in centre of 
alcove.

 

External air supply for ‘Caitec Air’ and cooling air

 

NOTE : 

Non

-

Combustible 

cladding eg :

 

10mm Promina Board, 
10mm Supalux,

 

Latex Plaster.

 

(not supplied)

 

Warm Air 
Vent

 

NOTE : 

50mm 

Clearance from the 
Flue Liner to Timber 

Description

 

 

 

TF 1500

 

TF 1200

 

TF 1000

 

To Centre of Flue

 

J

 

441

 

589

 

538

 

Flue Diameter

 

K

 

400

 

350

 

300

 

Liner Diameter

 

L

 

450

 

400

 

350

 

Heat Cell Clearance Width

 

M

 

1790

 

1690

 

1490

 

Heat Cell Clearance Depth

 

N

 

805

 

990

 

890

 

Heat Cell Clearance Height

 

O

 

2015

 

2150

 

2150

 

Hearth Width

 

P

 

2040

 

1800

 

1550

 

Hearth Depth

 

Q

 

300

 

750

 

600

 

Chimney Chase Clearance

 

X

 

550

 

500

 

450

 

Chimney Chase Clearance

 

Y

 

550

 

500

 

450

 

Summary of Contents for Traditional Fire - Gas 1000

Page 1: ...mm Promina Board 10mm Supalux Latex Plaster not supplied The fireplace is constructed and tested to comply with NZS 4558 int 2013 Decorative gas log and other fuel effect appliances Keep these instruc...

Page 2: ...Bricks H40 75X115X230mm Other Sizes Available Varied Fire Brick Refractite Mortar 1 Flashing System 1 Non Combustible Cladding Promat Superlux Brick Stone etc 10 1 Fill Crush vermiculite etc 1 Alumini...

Page 3: ...r area as they project the heat away from their opening The Topography of the land The slope and position of the land in relation to the home has a bearing on how the wind will interact with the fire...

Page 4: ...th G 1440 1640 1740 Heat Cell Height H 1820 1995 1860 Heat Cell Depth I 865 965 780 To Centre of Flue J 538 589 441 Flue Diameter K 300 350 400 Liner Diameter L 350 400 450 Heat Cell Clearance Width M...

Page 5: ...Flame Effect Output Only Effect Effect Effect Supply Pipe Size dia min 3 8 3 8 1 2 Natural Gas Nominal Pressure kPa 1 5 kPa 1 5 kPa 1 5 kPa Nominal Injector Size mm 2 X 1 8mm 2 X 2mm 2 X 2 4mm Burner...

Page 6: ...ir and cooling air NOTE Non Combustible cladding eg 10mm Promina Board 10mm Supalux Latex Plaster not supplied Warm Air Vent NOTE 50mm Clearance from the Flue Liner to Timber Description TF 1500 TF 12...

Page 7: ...th P 2040 1800 1550 Hearth Projection Q 300 750 600 Solid Poured Top Width RR 2390 2010 1610 Solid Poured Top Depth SS 1090 1200 1000 Block Enclosure Height TT 2390 2390 2390 Chimney Chase Clearance X...

Page 8: ...nly REFRACTORY FIRE BRICK AMOUNTS standard Brick size and refractite The standard brick out is the stretcher bond style but other styles can be bricked according to your liking Some Bricklayers prefer...

Page 9: ...Fit the Top Spider into position ensure that the legs of the spider are fitted inside the liner and that the spider is positioned hard down onto the liner and tighten with the screw and nut 3 Place t...

Page 10: ...1041 20th July 2004 FLUE PENETRATION Vented through alcove Double lined Flue System FLUE PENETRATION Vented through Top Flashing All external air vents and ceiling penetrations are to be vermin and r...

Page 11: ...AIR VENTILATION OPTIONS VENTING THROUGH CHIMNEY CHASE No Insulation under flashing VENTING THROUGH FLASHING Insulation under flashing Note Flashing spigot height is determined by the insulation that i...

Page 12: ...hange product specifications without prior notification All Dimension are in mm Copyright 12 FLUE HEIGHT MINIMUM DETAILS FRAME OUT AND TRIM OUT DETAILS FOR CHIMNEY CHASE Option X Singled Lined Flue Sy...

Page 13: ...ct specifications without prior notification All Dimension are in mm Copyright 13 COMBUSTIBLE MANTLE CLEARANCES HEARTH CLEARANCES Mantle Clearances Firebox Y Z TF 1000 1050 1400 TF 1200 1150 1600 TF 1...

Page 14: ...or the Installation and Commissioning of this Appliance and Flue System Check that the Gas Type Specified on the Data Plate is correct for the available supply LPG or NG A copper gas supply capable of...

Page 15: ...ositioned with the torn roughest facing outward Ensure coal positioning does not directly block the 3 flame pilot The placement of the Coals Logs may vary to make an even flame pattern Logs and Twigs...

Page 16: ...et but may require adjustment onsite Turn Appliance off remove front plastic cover on Igniter Pull cover to slide off Unscrew test nipple on the burner manifold fit the test gauge securely see diagram...

Page 17: ...rmington Gas decorative fire operates on the principle of dual radiant and convected heat Therefore it is important to observe the following precautions associated with any heating appliance or open f...

Page 18: ...The burner will operate any pressure between the hi and the low pressures DIAGRAM B SHOWING CONTROL VALVE WITH TEST POINTS AND ADJUSTING SCREW After checking the pressure turn the unit off remove man...

Page 19: ...Due to continued product improvement Warmington Ind LTD reserves the right to change product specifications without prior notification All Dimension are in mm Copyright 19 EG ON OFF ONLY SIT840 valve...

Page 20: ...logs or river rocks to achieve their full flame pattern and glow During the initial burn period some smoke and smell may be experienced Because of this run the appliance on the high po sition in a wel...

Page 21: ...16 Due to continued product improvement Warmington Ind LTD reserves the right to change product specifications without prior notification All Dimension are in mm Copyright 21 EG HI LOW SIT 843 valve W...

Page 22: ...sume the previous flame and fan settings unless the appliance was switched off due to power failure In the circumstance of a power failure the Remote Control System will return to the default settings...

Page 23: ...d until the fan is turned off Your remote control has all the features of the control receiver situated on the front panel of the burner By pressing Timer button the power LED will start flashing and...

Page 24: ...d check pressure NOTE Any alterations to pressure is to be carried out by a Certified Gasfitter If adjustments are necessary remove the cap The Pressure Adjustment screw and nut are on the front side...

Page 25: ...s See Diagram B above Turn the appliance on and off a few times to check ignition When you are satisfied that the appliance is working correctly fit the front panel assembly back to the gas burner NOT...

Page 26: ...Due to continued product improvement Warmington Ind LTD reserves the right to change product specifications without prior notification All Dimension are in mm Copyright 26 FULLY MODULATING SIT 845 val...

Page 27: ...t be installed in accordance with relevant standards and the appro priate building codes WARNINGS WARNING ANY MODIFICATION OF THE APPLIANCE THAT HAS NOT BEEN APPROVED IN WRIT ING BY THE TESTING AUTHOR...

Reviews: