warema_890558_alhb_en_v5•2022-02-01
We reserve the right to carry out improvements
30
Wisotronic 1-channel
Installation instructions
5.3.3 Sensor
The weather station multisense delivers all of the weather data needed to
efficiently utilise the wide range of automatic functions of the Wisotronic. It
simply needs to be connected with a 4-wire line.
1 2 3 4
RD
BK
YE
WH
4 x AWG 26 UL black
JY(St)Y 2 x 2 x 0.8mm
Onsite
junction
box
Terminal 1: 0 V
Terminal 2: 24 V
Terminal 3: A
Terminal 4: B
Weather station multisense
View from below
Strain relief
OG BN BK RD
RD
RD
BK
BK
YE
WH
BN
OG
Fig. 14
Weather station multisense connection
Terminal block X3 (terminals 1 to 4)
Permissible line cross section
0.12 to 0.5 mm
2
single-wire
Stripping length
6.5 mm
Maximum line length
200 m
Only use lines of type JY(St)Y 2x2x0.8 mm.
The Wisotronic automatically detects whether sensors are connected and
which ones.
CAUTION
If no sensors are connected, only the current room temperature is
displayed and nothing can be damaged on the control.
However, please
be aware that in this case, the sun shading control system cannot function
correctly and that this may result in damage to your sun shading system.
Depending on the mounting situation, you can also directly route the line of
type JY(St)Y to the weather station multisense. It must be ensured that the
line is protected against UV radiation (e.g. in a conduit, hose) along its entire
length. Mount the line in such a way that water cannot penetrate the device
or enter into the building.
Connection