3
2016158_0•en•2017_03_01
We reserve the right to make technical changes
Technical data
KNX SA 4MDC REG
min.
typ.
max.
Unit
Operating voltage (SELV)
21.6
24
26.4
V DC
Current consumption in
standby mode
6.0
mA
Current consumption with
four activated relays
45
mA
Output per drive
Switching capacity per
channel at 24 V DC
20
72
W
Interface KNX
TP 1
Current consumption KNX
3.5
13
mA
Voltage
29
V DC
Conformity
can be viewed at www.warema.com
This device complies with the EMC directives for use in
residential and commercial areas.
Ambient conditions
Operating temperature
0
50
°C
Storage temperature
0
70
°C
Humidity
(not condensing)
10
40
85
%F
rel
Connection
Connecting line
Screw terminals
KNX bus system, drives
Spring terminals
Wire cross sections
Supply line
24 V DC
max. 2.5 mm²
KNX bus system
0.6 - 0.8 mm
∅
Motor outputs
max. 1.5 mm²
Housing
Degree of protection
DIN rail-mounted housing
IP30
Safety class
(PE is looped through)
III
Miscellaneous
Automatic operation
Type 1
Software class
A
Location of use
clean ambient conditions
Article numbers
KNX SA 4MDC REG
2014 572
WAREMA Renkhoff SE
Hans-Wilhelm-Renkhoff Strasse 2
97828 Marktheidenfeld
Germany
60 mm
95 mm
90 mm
72 mm
4 MW
60 mm
Fig. 3
Dimensions of 4 MW DIN rail-mounted housing for
KNX SA 4MDC REG.