Installation instructions

KNX SA 16M230 SMI REG

KNX SA 16MDC SMI LoVo REG

Keep for future use!

Valid from 1st December 2018

2024843_0•en•2018-12-01

We reserve the right to make technical modifications

1

WARNING

If hazard-free operation cannot be as-

sumed, the device may not be started or 

must be deactivated. This assumption is 

justified if:

 

  

the housing or the connecting lines show 

signs of damage, 

 

 

the device is no longer working.

WARNING

It is important to comply with the fol-

lowing points in the interest of personal 

safety.

  Children may not play with the operating elements of 

the control unit or the remote control. Store remote 
controls out of reach of children.

  Make sure that no persons or objects are in the path 

of the driven parts (venetian blinds, external venetian 
blinds, etc.).

  Disconnect the device from the supply voltage if clean-

ing or other maintenance work must be performed.

Function of the sun shading actuator

You will find a detailed description of the software 

functions for the KNX  sun shading actuators in the 

KNX SA SMI software manual  

(art. no. 2024839). You can download the manual and the 

product database of the sun shading actuator from www.

warema.de/knx or from the ETS online catalogue.

Installation

The device is intended for installation in a distribution 

cabinet. The device is installed by clipping it onto a DIN 

rail (TH 35/DIN 60715)

Electrical connection

An on-site overload current protection device (fuse) and a 

disconnecting and isolating switch to switch off the entire 

system must be provided.
The electrical connection is made as shown in the wiring 

diagram on the reverse side (Fig. 7), the connection to 

the KNX bus system and the drives is made using spring 

terminals, the connecting lines are designed as screw 

terminals. 

General information

Fig. 1 

 KNX SA 16M230 SMI REG /  

KNX SA 16MDC SMI LoVo REG 

The KNX SA 16M230 SMI REG and the 

KNX SA 16MDC SMI LoVo REG sun shading actuators 

are devices for the central operation of up to 16 SMI sun 

shading drives in up to 16 groups.

The device is operated using a KNX bus system. The sun 

shading actuator are supplied via the KNX bus. The SMI 

interface is, however, operated via a  

230 V AC auxiliary voltage.

The drives are directly operated with either 230 V AC or 

a separate 24 V DC power supply unit with, depending 

on requirements. A maximum of 16 motors without fuse 

protection can be connected to the SMI interface.

Intended use

The KNX SA 16M230 SMI REG and KNX SA 16MDC 

SMI LoVo REG have been developed to control SMI sun 

shading products. The approval of the manufacturer must 

be obtained for any use of the device other than its intend-

ed purpose specified in these instructions.

The sun shading actuator is intended for installation in 

enclosed electrical operating facilities.

Safety instructions

WARNING

The electrical installation must be per-

formed by a certified electrician in accord-

ance with the electrical installation regu-

lations published by the VDE Association 

for Electrical, Electronic & Information 

Technologies (VDE 0100) or the standards 

and legal requirements of the country in 

which the device is being installed. The 

electrician must observe the installation 

instructions included with the electrical 

devices supplied.