background image

Page | 6 

 

GENSET QUICK START/STOP CHECKLIST

 

These instructions are for starting the generator set in Manual Mode.  
 

Read the entire genset Operator Manual before starting the engine 

 

Pre-Startup Checks 

Check coolant level, oil level and confirm that you have sufficient fuel. 

Confirm the Fuel Valve is in the correct position for the fuel source (skid tank or external supply). 

Confirm the Estop button is in Run mode (turn it clockwise to release). 

Place the Battery Switch in the ON position. 

 

Control Panel 

Confirm the Main Circuit Breaker is in the OFF position. 

Turn the Deepsea controller ON and address any alerts or warnings. 

Press the red Stop/Reset button and then the Manual Mode button. 

Press the green Start button and wait a few seconds for the engine to start. 

Allow the engine to warm up, then switch the Main Circuit Breaker ON. 

Monitor the generator and loads as needed to assure proper operation. 

 

Shutting Down the Genset 

Do not use the Estop button to stop the generator except in an emergency 

Confirm that your loads are ready to lose power. 

Switch the Main Circuit Breaker OFF 

Press the Stop/Reset button to stop the engine. 

Turn the Deepsea controller OFF. 

Place the Battery Switch in the OFF position to avoid battery drain between uses. 

 
 
 
 
 
 
 
 
 

Summary of Contents for WSP12

Page 1: ...Silent Power Series Generator Operator Manual Model WSP12 with DSE6020 Controller PN 221235 ...

Page 2: ...re to properly follow these precautions can result in property damage serious injury or death Indicates a possibility of personal injury or equipment damage if instructions are not followed Gives helpful information If you need assistance with your generator set please contact our service department using the following information Wanco Inc 5870 Tennyson Street Arvada Colorado 80003 303 427 5700 f...

Page 3: ... COMMON SERVICE PARTS 13 7 TROUBLESHOOTING 13 8 SPECIFICATIONS 14 9 WIRING DIAGRAM 15 10 TOWING 16 Read and understand this Operator Manual before starting the generator Failure to do so could result in personal injury or equipment damage Refer to the Perkins Engine Operation Maintenance Manual for important engine specific information ...

Page 4: ...or death Only qualified service personnel should attempt to service the generator electrical systems Explosion Hazard Keep Engine fuel and other combustibles away from sparks open flame and burning objects Do not smoke near the generator Stop the engine before filling or draining the fuel tank Use only diesel fuel do not fuel with gasoline Replace the fuel tank cap after refueling Do not use gasol...

Page 5: ...erator controls Moving Parts Hazard Disconnect the cranking battery negative terminal and or disengage the battery at the Battery Disconnect Switch before servicing any part of the engine alternator or generator controls Risk of Sever Burns Do not touch the exhaust system or areas near the exhaust at rear of trailer Do not remove radiator cap when engine is hot Contents are hot and under pressure ...

Page 6: ...t Breaker is in the OFF position Turn the Deepsea controller ON and address any alerts or warnings Press the red Stop Reset button and then the Manual Mode button Press the green Start button and wait a few seconds for the engine to start Allow the engine to warm up then switch the Main Circuit Breaker ON Monitor the generator and loads as needed to assure proper operation Shutting Down the Genset...

Page 7: ... operator s position Generator right side view from operator s position Lift Hook Coolant Drain Forklift Access 2X Control Panel Emergency Stop Switch Receptacles Circuit Breakers Oil Drain Containment Vessel Cleanout Diesel Tank Drain External Diesel Connections ...

Page 8: ...d of the generator Refer to the DSE6020 Mk II Operators Manual for additional information Menu Navigation Use the Up Down Navigation Buttons to access various menus Menu Navigation Buttons Stop Reset Mode Manual Mode Auto Mode Mute Alarm Lamp Test Start Engine Manual Mode only Display ...

Page 9: ...onnection panel on the generator right side The Emergency Stop Switch shuts down the engine immediately for Emergency use only See the Operating Section for instructions on normal engine shutdown Circuit Breakers for Receptacles 120V GFCI Receptacles 120 240V CS6369 Receptacles 120V NEMA TT30 RV Receptacle 120 240V NEMA L14 30 Receptacle Main Circuit Breaker ...

Page 10: ...ections When in the OFF position no current or voltage will be present at any AC output connection This circuit breaker may switch OFF during operation if it detects an overload condition Battery Disconnect Switch Located inside the engine compartment on the generator right side Disconnects the cranking battery from all 12VDC systems including the controller and relays This switch must be ON for t...

Page 11: ... the Controller Press and release the Manual Mode button on the Controller Press and release the Start Engine button on the Controller The engine will start after a few seconds of glow plug engagement Allow the engine to warm up for a few minutes before applying load Stopping the engine in Manual Mode Emergency shutdown Press the Emergency Stop Button located beside the electrical connection panel...

Page 12: ...ion for leaks loose parts etc 50hrs or Weekly Drain water and sediment from the main fuel tank 250hrs or every 6mo Inspect adjust engine alternator and fan belts 500hrs or every 12mo Replace the fuel system filter Check battery electrolyte level Test coolant add Supplemental Coolant Additive SCA as needed Clean replace air cleaner element Replace engine oil and filter Inspect replace fluid hoses a...

Page 13: ...oblem Common Solutions The Deepsea controller display is blank Confirm the Battery Disconnect Switch is closed The engine will not crank Check all battery cables for damage Confirm the battery voltage is at least 12 0 volts The engine cranks but will not start Confirm sufficient fuel is in the fuel tank Confirm battery voltage is at least 12 0 volts The engine shut down unexpectedly Review any ala...

Page 14: ... BCI Group 51 450 CCA 12VDC Engine Brand Model Perkins 403F 15G EPA Emission Compliance EPA Tier IV Final Cylinders Displacement 3 1 5 Liter Coolant Capacity 1 6 gallons Lube Oil Capacity 1 6 gallons Fuel Type Diesel ULSD Alternator Mecc Alte ECP28 S 4 Frequency 60 hz Voltage Regulator Mecc Alte DSR Excitation Boost Mecc Alte MAUX Dimensions L x W x H 72 in L x 32 in W x 51 in H Weight dry w o tra...

Page 15: ...Page 15 WIRING DIAGRAM ...

Page 16: ...s a removable drawbar ensure the drawbar is attached securely to the trailer frame with two sets of bolts washers and nuts The bolts should engage the drawbar and the nuts should be tight Lower the drawbar jack into the down position by pulling the jack locking pin and rotating the jack downward Release the pin and continue rotating the jack until it is vertical When the jack is properly set the l...

Page 17: ...e serious injury or death During towing Failure to properly follow these precautions can result in property damage serious injury or death Do not tow the trailer with any people parts supplies or additional equipment attached to the trailer or loaded onto it Do not tow additional trailers or other equipment in tandem with the message sign trailer The recommended maximum speed for highway towing is...

Page 18: ...fter towing unhook the tow chains from the tow vehicle then use the drawbar mounted jack to raise the drawbar and release the drawbar hitch from the tow vehicle Pull the vehicle away from the message sign trailer when ready ...