GENSET QUICK START/STOP CHECKLIST
These instructions are for starting the generator set in Manual Mode.
Read the entire genset Operator Manual before starting the engine
Pre-Startup Checks
Check coolant level, oil level and confirm that you have sufficient fuel.
Confirm the Fuel Valve is in the correct position for the fuel source (skid tank or external supply).
Confirm the Estop button is in Run mode (turn it clockwise to release).
Place the Battery Switch in the ON position.
Control Panel
Confirm the Main Circuit Breaker is in the OFF position.
Turn the Deepsea controller ON and address any alerts or warnings.
Press the red Stop/Reset button and then the Manual Mode button.
Press the green Start button and wait a few seconds for the engine to start.
Allow the engine to warm up, then switch the Main Circuit Breaker ON.
Monitor the generator and loads as needed to assure proper operation.
Shutting Down the Genset
Do not use the Estop button to stop the generator except in an emergency
Confirm that your loads are ready to lose power.
Switch the Main Circuit Breaker OFF
Press the Stop/Reset button to stop the engine.
Turn the Deepsea controller OFF.
Place the Battery Switch in the OFF position to avoid battery drain between uses.