5.3
Output 1 Menu
The Out 1 menu is used to set the control set point, and to configure the
timer/totalizer to keep track of replenishment in the desired way. This menu
provides the following settings: Total 1, Set Point, Dead Band, Time Limit,
Interlock, and H O A.
The top level menu status line may display the following messages: Off, Intrlck,
Timeout, or a time. "Off" indicates that the output is off. "Intrlck" indicates that the
output would be on but is not because of a signal from a flow switch or level switch
is stopping control. "Overrun" indicates that the output has been on for longer than
the maximum time programmed by the user. The time shows how long the output
has been on.
Total 1
Press
ENTER
to program the timer/totalizer functions.
Reset Total Y/N
Use the arrow keys to toggle between Y(Yes) and N(No) to reset the totalizer.
Total As
Press
ENTER
, then use the Up and Down arrows to choose whether to totalize in
units of time, volume or copper metal turnovers.
Turnover Lim.
Only appears if you choose to totalize by metal turnovers. Use the arrow keys to
enter the maximum number of turnovers. The controller will prompt you when this
number has been exceeded.
Turn Vol(G or L)
Only appears if you choose to totalize by metal turnovers. Enter the number of
gallons (G) or liters (L) that equals one metal turnover. The unit of measure
displayed correlates with that of the rate units selected in the next menu.
Rate Units
Only appears if you choose to totalize by volume or metal turnovers. Press
ENTER,
then use the arrow keys to toggle between Gallons per Hour, mL per minute or
Liters per hour. These units of measure will be used to enter the rate at which the
replenishment pump adds chemicals.
Pump Rate
Only appears if you choose to totalize by volume or metal turnovers. Use the arrow
keys to set the flow rate of the replenishment pump.
Set Point
Use the arrow keys to adjust the display to read the desired set point value of the
bath. Press
ENTER
to accept the change.