Walchem W900 Series Quick Programming Manual Download Page 2

 

       W900 Quick Programming Guide 

 

 

Programming Inhibitor Feed 

1.

 

From the main menu, press   

Outputs

 

2.

 

Select the relay you want to use for the inhibitor feed pump 

3.

 

Press Configuration    

4.

 

Press the DOWN Arrow until you get to MODE 

5.

 

Choose the feed mode you want, and then Check   

6.

 

Press Configuration     again. 

7.

 

If you set the mode for Bleed and Feed,  press the Down Arrow until you get to Bleed 

8.

 

Press Bleed, and then select the relay that has been programmed for the bleed valve. 

9.

 

Press Check   

10.

 

Press the UP or DOWN Arrow, then HOA setting. Select Auto 

 

Programming Biocide Additions 

 

1. From the main menu, press     Outputs  
2. Select the relay you want to use for the biocide pump.  
3. Press Configuration   
4. Press the Down Arrow until you get to Mode  
5. Select Biocide Timer, and Check   
6. Press Configuration   
7. Press Event 1  
8. Screen should say Repetition None. Press this.  
9. Using the Down arrow, you can choose Daily, 1 Week, 2 Week or 4 Week.  
10. When you press Daily, you will be prompted to enter a Start Time, and the Duration. This event will 

repeat every day. If you want more than one event per day you can add additional events. Just press 

Event 2 to Event 10 to program. When you press 1 Week you will be prompted to enter a day of the 

week, start time and duration. Again, you can repeat this on events 2-10 if you want more events 

repeating every week. You can also enter events based on a 2 week and 4 week timer.  
11. After the events have been programmed, you can press the down arrow to program a pre-bleed, 

bleed lockout, as well as interlocking other channels.  

 

 

 

 

 

 