background image

18 

Device Description 

WAGO WINSTA® 770 

 

 

770-629/130-000 WINSTA® Sunblind Box 4 Channel 

 

Manual 

 

Version 1.1.1, valid from HW/FW version XXXX0201XX 

Table 7: Bus/central connection 

Function 

Connection 

Designation 

Bus 

Central 

1 B 

 

N.C. 

2 A 

GND 

3 N.C. 

Down 

 

1

2

3

4

1

2

3

4

WAGO

770-244 (Buchse)

770-504/023 (Gehäuse)

WAGO

770-244 (Buchse)

770-504/023 (Gehäuse)

 

Figure 8: Bus/central connection 
 

4 N.C. 

Up 

 

 

 

 

 

Activation via the WAGO-I/O-SYSTEM 750 

The following module is required to activate via bus signal/RS485 and WAGO-
I/O-SYSTEM: 
RS-485 serial interface, adjustable; item number 750-653/003-000. 

 

Summary of Contents for WINSTA Sunblind Box

Page 1: ...anual WAGO WINSTA 770 WINSTA Sunblind Box 4 Channel 770 629 130 000 Version 1 1 1 valid from HW FW version XXXX0201XX Pos 3 Alle Serien Allgemeine Module Hinweise zur Dokumentation Impressum allgemein...

Page 2: ...571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never be ful...

Page 3: ...on 12 3 1 View 13 3 2 Labeling 14 3 3 Connectors 15 3 3 1 Connection Overview 15 3 3 2 230V Supply 16 3 3 3 Motors 16 3 3 4 Local Push Buttons 17 3 3 5 Bus Central Connection 17 3 3 6 Screening 19 3 4...

Page 4: ...7 4 3 1 A Group Moving Motors 1 to 4 Simultaneously 37 7 4 3 2 Two Groups Moving Motors 1 and 2 and Motors 3 and 4 Simultaneously 37 7 4 3 3 Two Groups Moving Motors 1 2 and 3 Simultaneously Motor 4 M...

Page 5: ...21 doc 46994 2 1 1 1 Scope of Validity This documentation applies to the WINSTA box 770 629 130 000 WINSTA Sunblind Box 4 Channel from HW FW version XXXX0201XX Pos 10 Serie 770 Winsta Boxen Hinweise z...

Page 6: ...if not avoided will result in death or serious injury Personal Injury Indicates a moderate risk potentially hazardous situation which if not avoided could result in death or serious injury Personal In...

Page 7: ...annel Manual Version 1 1 1 valid from HW FW version XXXX0201XX Additional Information Refers to additional information which is not an integral part of this documentation e g the Internet Pos 11 4 Dok...

Page 8: ...Font Conventions Table 2 Font Conventions Font type Indicates italic Names of paths and data files are marked in italic type e g C Programme WAGO I O CHECK Menu Menu items are marked in bold letters...

Page 9: ...0 3 1 2 1 1 Subject to Changes WAGO Kontakttechnik GmbH Co KG reserves the right to provide for any alterations or modifications that serve to increase the efficiency of technical progress WAGO Kontak...

Page 10: ...Wichtige Erl uterungen Sicherheitshinweise Achtung Achtung Defekte oder besch digte Ger te austauschen 6 mod_1260180857358_21 doc 46743 1 Replace defective or damaged devices Replace defective or dama...

Page 11: ...d electrostatic discharge The devices are equipped with electronic components that you may destroy by electrostatic discharge when you touch Pay attention while handling the devices to good grounding...

Page 12: ...d slat sunblind mode selection are performed via DIP switch Operating the boxes in a network configuration provides extended functionality 1 The sunblinds of all connected boxes can optionally be move...

Page 13: ...2 S3 S4 1 2 N 1 2 N N 2 1 N 2 1 N L 4 3 2 1 1 2 3 4 5 6 ON DIP 1 2 3 4 5 6 ON DIP 1 2 3 4 5 6 ON DIP S6 S5 S7 230 V Jumper 8 7 10 10 10 10 1 2 3 9 4 5 6 2 7 7 7 Figure 1 View Table 3 Legend for View f...

Page 14: ...e designation the most important device data the marking field for the address the serial number and the pin assignments for the connectors Marking field for address To make identification even easier...

Page 15: ...984262656_21 doc 31961 2 1 3 3 Connectors Pos 26 Serie 770 Winsta Boxen Ger tebeschreibung Anschl sse Anschl sse 0770 0629 0130 0000 6 mod_1255677975461_21 doc 42970 333333 1 3 3 1 Connection Overview...

Page 16: ...r with the designation 230 V The connection is fused with a 6 3 A fuse Table 4 Connection of 230V supply Connection Designation Function L L PE PE L PE N L PE N WAGO 770 103 WAGO 770 103 Figure 5 Conn...

Page 17: ...The type of activation of the box can be selected with the help of an IDC connector jumper At the factory bus operation activation via RS485 signal is pre set Alternatively by changing the jumper it i...

Page 18: ...nection Designation Bus Central 1 B N C 2 A GND 3 N C Down 1 2 3 4 1 2 3 4 WAGO 770 244 Buchse 770 504 023 Geh use WAGO 770 244 Buchse 770 504 023 Geh use Figure 8 Bus central connection 4 N C Up Acti...

Page 19: ...The screening should be laid at the entrance to the cabinet or housing in order to catch interference right at the entrance The screening of the bus line is described in the respective configuration...

Page 20: ...e Serien Allgemeine Module berschriften f r alle Serien Bedienelemente berschrift 2 4 mod_1239191655456_21 doc 30439 2 1 3 5 Operating Elements Pos 31 Serie 770 Winsta Boxen Ger tebeschreibung Bediene...

Page 21: ...he sunblind box has an IDC connector for a jumper bridge with which it is possible to select whether the box should be activated via a bus signal RS485 or via a 24V signal central operation DIP Modul...

Page 22: ...eneral Dimensions W x H x D without connector plug 200 mm x 145 mm x 30 mm Weight 450 g Type of mounting Wall screw fixing Assembly Interior area e g intermediate floors suspended ceiling Fitting posi...

Page 23: ...ansmission medium Control line J Y St Y 2 x 2 x 0 6 mm2 max 10 m Connection type Female connector 3 pole Item No 734 103 Snap on strain relief housing Item No 734 603 3 6 5 Outputs Table 13 Technical...

Page 24: ...e 9 600 baud Max number of bus participants 16 Transmission medium Screened bus cable YCYM 2 x 2 x 0 8 mm2 max 800 m Central control via 24VDC signal Operating voltage DC 24 V 10 50 Current consumptio...

Page 25: ...55687_0 doc 24460 1 Pos 40 Alle Serien Allgemeine Module berschriften f r alle Serien Normen und Richtlinien berschrift 2 4 mod_1242804031875_21 doc 33646 2 1 3 8 Standards and Guidelines Pos 41 Serie...

Page 26: ...653 003 000 via which the WAGO I O SYSTEM as the superior controller can access up to 16 boxes per bus segment This operating mode addresses both individual channels and groups of boxes Additional in...

Page 27: ...unction is suitable for interior or exterior blinds whose slats can be adjusted horizontally in order to regulate light coming in e g classic sun protection The sunblind moves in the desired direction...

Page 28: ...ew holes Pos 50 Alle Serien Allgemeine Module berschriften f r alle Serien Ger te anschlie en berschrift 1 3 mod_1234172889468_21 doc 27460 1 1 6 Connect Devices Pos 51 Serie 770 Winsta Boxen Anschlie...

Page 29: ...ion without Voltage Monitoring On principle the configuration of a central operation e g central switch timer should take place according to the following scheme L N PE 230 V AC 24 V DC Central Connec...

Page 30: ...al Control GND up down Figure 12 Wiring of the Winsta sunblind boxes with monitoring In central operation with voltage monitoring 0V levels are evaluated as a control signal If neither of the 24V leve...

Page 31: ...me B 120 W L N PE A 120 W Bus Connection Central Control Figure 13 Wiring of the Winsta sunblind boxes in a bus system Don t forget the bus end module The bus must be connected at the beginning and en...

Page 32: ...ges to these settings will be explained below Only make the setting when the device is de energized In order not to damage the sunblind box settings on the box shall only be made when it is de energiz...

Page 33: ...485 or via a 24V signal central operation DIP Modul 2 4 3 2 1 ON DIP ON DIP S7 Jumper Figure 14 IDC connector for jumper bridge 7 3 1 Bus Operation If the jumper bridge is plugged in the viewing direc...

Page 34: ...7 3 2 Central Operation If the jumper bridge is plugged in the viewing direction of the figure above into the two upper pins 24V activation is selected S3 Figure 16 Jumper setting for central operati...

Page 35: ...ouping of the motors the moving time and the moving logic DIP Modul 2 DIP Modul 1 M3 4 3 2 1 1 2 3 4 5 6 ON DIP 1 2 3 4 5 6 ON DIP 1 2 3 4 5 6 ON DIP S6 Jumper S7 S5 Figure 17 DIP switch module 7 4 1...

Page 36: ...setting of bus addresses is only possible in bus operation For Central operation de activate switches 1 to 5 of DIP Module 1 address 0 Set the bus address with the switches 1 to 5 of the DIP module 1...

Page 37: ...Motors 1 and 2 and Motors 3 and 4 Simultaneously To form two groups Group A in which motors 1 and 2 and Group B in which motors 3 and 4 move together make the following settings Table 18 Two groups mo...

Page 38: ...4 move simultaneously Assignment of motors local push buttons Motor 1 2 3 4 ON DIP 1 2 3 4 5 6 ON DIP 1 2 3 4 5 6 Figure 23 Three groups motors 1 and 2 move individually motors 3 and 4 move simultane...

Page 39: ...ng Make the following settings to activate bus failure monitoring voltage monitoring ON DIP 1 2 3 4 5 6 Figure 26 Operation with bus failure monitoring voltage monitoring Voltage Monitoring in Central...

Page 40: ...inute or 4 minutes 7 4 5 1 Operating Time 1 Minute In order to set an operating time of 1 minute make the following settings ON DIP 1 2 3 4 5 6 Figure 27 Operating time 30 seconds Factory setting This...

Page 41: ...ction with switch 6 of the DIP module 2 to sunblind or slat function 7 4 6 1 Sunblind Function To select sunblind operation make the following settings ON DIP 1 2 3 4 5 6 Figure 29 Sunblind function F...

Page 42: ...necessary The positions are lost in case of a power failure After a loss of supply voltage all stored sunblind positions are lost After a completely executed reference operation to any end position t...

Page 43: ...2 1 1 8 Diagnostics Pos 60 Serie 770 Winsta Boxen Diagnose Diagnose 0770 0629 0130 0000 7 mod_1268228638180_21 doc 52231 1 Diagnosis can be undertaken with the function module FbWinsta_BC_Box Addition...

Page 44: ...70 629 130 000 Table 22 Accessories Description Item No RS 485 serial interface for modular WAGO I O SYSTEM 750 freely configurable 750 653 003 000 Plug set for WINSTA sunblind box Includes 1 x socket...

Page 45: ...unblind boxes in a bus system 31 Figure 14 IDC connector for jumper bridge 33 Figure 15 Jumper setting for bus operation 33 Figure 16 Jumper setting for central operation 34 Figure 17 DIP switch modul...

Page 46: ...chnical data General 22 Table 10 Technical data Environmental conditions 22 Table 11 Technical Data Supply 22 Table 12 Technical data Inputs 23 Table 13 Technical data Outputs 23 Table 14 Technical da...

Page 47: ...STA 770 47 770 629 130 000 WINSTA Sunblind Box 4 Channel Manual Version 1 1 1 valid from HW FW version XXXX0201XX Pos 69 Dokumentation allgemein Gliederungselemente Leerseite 3 mod_1219230851078_0 doc...

Page 48: ...mod_1285229376516_21 doc 64944 1 WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 49 5 71 8 87 0 Fax 49 5 71 8 87 1 69 E Mail info wago com Internet htt...

Reviews: