3.6.4.1 Connection
Sensors and actuators can be directly connected to the relevant channel of the
I/O module in 1, 2, 3 or 4 conductor connection technology. The I/O module
supplies power to the sensors and actuators. The input and output drivers of
some I/O modules require the field side supply voltage.
Pos: 19.16.29 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembeschr eibung/Versorgung/F eldversorgung - Anschl uss - Ei nspeisung fel dsei tig (ECO) @ 3\mod_1232950087031_21.docx @ 26708 @ @ 1
The power supply modules provide field side power (24 VDC). In this case it is a
passive power supply without protection equipment. Power supply modules are
available for different potentials, e.g. 24 VDC, 230 VAC or others.
Pos: 19.16.30 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembeschr eibung/Versorgung/F eldversorgung - Anschl uss - Potentialgruppen mit Einspeisemodul XTR @ 17\mod_1382697121058_21.docx @ 135120 @ @ 1
Power supply modules with or without diagnostic capability are available for the
power supply of other field potentials (e.g. 24 VDC, 0 VAC/DC … 230 VAC/DC,
120 VAC, 230 VAC). The power supply modules can also be used to set up
various potential groups. The connections are connected in pairs to a power
contact.
Pos: 19.16.31 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembeschr eibung/Versorgung/F eldversorgung - Anschl uss - Bild: F el dversorgung (XTR F el dbuskoppl er) @ 18\mod_1392711163003_21.docx @ 145733 @ @ 1
Figure 8: Field supply (sensor/actuator) (example)
Pos: 19.16.32 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembeschr eibung/Versorgung/F eldversorgung - Leg ende zu Abbildung F el dversorgung für Fel dbuskoppl er @ 18\mod_1392714538509_21.docx @ 145743 @ @ 1
Table 6: Legend for the “Field supply (sensor/actuator)” figure
Position Beschreibung
1
Field supply 24 VDC
2
Field supply 0 V
3
Power jumper contacts (potential distribution to adjacent I/O modules)