WAGO-I/O-SYSTEM 750 XTR
Use in Hazardous Environments 259
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
Pos: 106.16 /Seri e 750 ( WAGO-I/O-SYSTEM)/Einsatz in Ex- Ber eichen/Beispiel bedr uckung und T extdetail CEC _2017 @ 29\mod_1497865583297_21.docx @ 424736 @ @ 1
Figure 65: Text Detail – Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Table 309: Description of Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Marking
Description
Dust
Ex
Explosion protection mark
nA
Type of protection
[ia IIIC]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)
X
Symbol used to denote specific conditions of use
Gases
Ex
Explosion protection mark
nA
Type of protection
[ia Ga]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 0
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)
X
Symbol used to denote specific conditions of use