192 Fieldbus Communication
WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
Pos: 96.3 /Serie 750 (WAGO-I/O-SYST EM)/F unktionsbeschr eibung/Fel dbuskommuni kati on/EtherNetIP/Erläuterung zur Objektbeschr., Kl assen Identi ty, M essage Router @ 3\mod_1233730204656_21.docx @ 27053 @ 444 @ 1
11.3.5.3 Explanation of the Table Headings in the Object Descriptions
Table 168: Explanation of the table headings in the object descriptions
Table heading
Description
Attribute ID
Integer value which is assigned to the corresponded attribute
Access
Set:
The attribute can be accessed by means of Set_Attribute services.
Response also possible with Get_Attribute service!
All the set attributes can also be accessed by means of
Get_Attribute services.
Get:
The attribute can be accessed by means of Get_Attribute services.
Get_Attribute_All:
Delivers content of all attributes.
Set_Attribute_Single:
Modifies an attribute value.
Reset:
Performs a restart.
0: Restart
1: Restart and restoration of factory settings
NV
NV (non volatile):
The attribute is permanently stored in the controller.
V (volatile):
The attribute is not permanently stored in the controller.
Without specifying, the attribute is not saved!
If this column is missing, all attributes have the type V
(volatile).
Name
Designation of the attribute
Data type
Designation of the CIP data type of the attribute
Description
Short description for the Attribute
Default value
Factory settings
11.3.5.4 Identity (01
hex
)
The “Identity” class provides general information about the fieldbus
coupler/controller that clearly identifies it.
72
hex
Discrete Output Point Extended 3
73
hex
Analog Input Point Extended 3
74
hex
Analog Output Point Extended 3
80
hex
Module Configuration
81
hex
Module Configuration Extended 1