14
•
750-483 [2 AI DC 0-30 V, Differential Measurement Input]
Process
Image
WAGO-I/O-SYSTEM
750
I/O
Modules
Approvals (cf. Chapter 2.2 of the Coupler/Controller Manual)
C
UL
US
(UL508)
ABS (American Bureau of Shipping)
BV (Bureau Veritas) (applied for)
DNV (Det Norske Veritas)
Cl. B
GL (Germanischer Lloyd)
Cat. A, B, C, D (EMC 1)
KR (Korean Register of Shipping)
LR (Lloyd's Register) (applied for)
Env. 1, 2, 3, 4
NKK (Nippon Kaiji Kyokai)
PRS (Polski Rejestr Statków)
RINA (Registro Italiano Navale)
C
UL
US
(ANSI/ISA 12.12.01)
Class I Div2 ABCD T4
DEMKO / IEC
I M2 / II 3 G/D Ex nA IIC T4
Conformity Marking
More Information
Detailed references to the approvals are listed in the document "Overview
Approvals WAGO-I/O-SYSTEM 750", which you can find on the CD ROM
ELECTRONICC Tools and Docs (Item-No.: 0888-0412)
or in the internet under:
Æ
Documentation
Æ
WAGO-I/O-SYSTEM 750
Æ
System Description
2.1.1.6 Process
Image
The analog input module 750-483 transmits 16-bit measured values and
8 optional status bits per channel.
The digitalized measured value is transmitted in a data word (16 bits) as input
byte 0 (low) and input byte 1 (high) into the process image of the coupler /
controller.
This value is represented with a 14 bit resolution on bit B1 ... B14.
The states of the two first least significant bit B0 are not defined in the range
from 0 V to 30 V.
Therefore, they are represented with a ‘X‘ in the table.
The hexadecimal and decimal measured values are listed in the table assuming