9970-0966
s07870000_00000005
V1.0.0 © 2016
WAGO Kontakttechnik GmbH & Co. KG
Hansastr. 27
D-32423 Minden
www.wago.com
En
Operating and Assembly instructions
Please keep!
Subject to design changes
Support: Phone: +49 (0) 571/8 87 - 5 55 / Fax: +49 (0) 571/8 87 - 85 55
Mail: [email protected]
EPSITRON
®
COMPACT Power
PE
L
N
DC+
DC+
DC -
DC -
DC power supply
787-1202 / 787-1212 /
787-1216 / 787-1226
1 Safety Information
1.1 General
Do not work when devices are energized!
High voltage can cause electric shock or burns.
Switch off all power to the device prior to performing any installation, repair or main
-
tenance work.
Live parts are likely to be touched!
The party setting up the device is responsible for providing appropriate touch guards.
The installation regulations must be observed for each individual application.
i
Only valid in conjunction with the device‘s manual!
These instructions are only applicable in conjunction with the device‘s manual!
This manual is available on the Internet at www.wago.com.
In addition, please observe the information provided on the device’s housing.
Please especially observe the following:
• The device described in these instructions shall only be installed by a qualified electrician
according to both DIN EN 50110-1/-2 and IEC 60364.
• Before startup, check the device for any damage that may have occurred during shipping. The
device shall not be put into operation in the event of mechanical damage.
• Ensure proper handling to protect device during shipping and handling. Parts must not be bent
and electrical spacing must remain constant.
• Only install this device in closed electrical service locations in accordance with
DIN EN 50178.
• Only install this device in dry indoor rooms.
• Do not install the devices on or in the vicinity of easily flammable materials.
• Keep sufficient distance from adjacent components to avoid interfering with the cooling!
• When used in accordance with EN 60335, the operator must provide a suitable mains isolator
in the device supply line
Improper use and failure to follow these instructions for use will render the warranty or guarantee null
and void.
1.2 Special Notes on Use as a DIN-Rail Built-in Installation Device
Ensure contact protection when used as a DIN-rail built-in installation device!
When used as a DIN-rail built-in installation device according to DIN 43880 (domestic
installation), the electrical installer must provide appropriate contact protection.
Only use the device 787-1202 or 787-1212 as a DIN-rail built-in installation device
with the front panel fitted.
2 Technical Data
Table 1: Device
787-1202
787-1212
787-1216
787-1226
Dimensions (mm) W × H × D
Depth including fastening clips (mm)
54 × 56 × 90
120
72 × 56 × 90
120
108 × 56 × 90
120
144 × 56 × 90
120
Weight
210 g
270 g
415 g
510 g
Table 2: Wiring
Cross section
0.2 mm² … 2.5 mm² / AWG 24 … 12
Strip length
9 mm … 10 mm / 0.35 in … 0.39 in
Select conductor cross sections as required for current load!
In the event of a fault, the output current of a power supply can be up to 2 × I
OUT
.
Only use conductor cross sections designed for this current load.
Table 3: Mounting
Mounting position
(Other mounting positions on request)
Distances
Top
Bottom Front
Rear
Left
Right
Vertical mounting (front panel front)
70 mm 70 mm 70 mm
---
0 mm
0 mm
Horizontal mounting (front panel top)
70 mm
---
70 mm 70 mm 20 mm 20 mm
Horizontal mounting (front panel bottom)
---
70 mm 70 mm 70 mm 20 mm 20 mm
3 View
Table 4: View (Example: 787-1226)
g
h
j
i
f
e
d
c
b
a
Pos. Assignment
a
Fastening clips for screw mounting
(included)
b
picoMAX
®
5 input (N L PE)
c
picoMAX
®
5 output (+ + - -)
d
Potentiometer for setting the output
voltage between 22 VDC … 26 VDC
e
LED indicator
LED green: Output voltage present
f
Front panel
787-1202 / 787-1212: removable
787-1216 / 787-1226: not removable
g
Type plate
h
Ventilation slots
i
Mount/removal latch on a DIN-rail
j
Slide switch for setting the input voltage
range (only 787-1226):
110 V
100 VAC … 120 VAC
230 V
200 VAC … 240 VAC
4 Mounting
Install the device vertically to ensure proper heat dissipation (ventilation slots above and below).
The following values should not be exceeded when installing with the front panel at the top or
bottom:
• Output power:
50 % (787-1202 / 787-1212 / 787-1216)
40 % (787-1226)
• Ambient temperature:
55 °C
Other mounting positions should only be used at one‘s own risk!
Avoid electrostatic discharge!
The devices are equipped with electronic components that you may destroy by
electrostatic discharge when you touch. Please observe the safety precautions against
electrostatic discharge in accordance with DIN EN 61340-5-1/-3
.
Pay attention while
handling the devices to good grounding of the environment (persons, job and packing).
4.1 DIN 35 Rail
1.
2.
2.
1.
Figure 1: Mounting
Figure 2: Removal
4.1.1 DIN-Rail Mounting
Install the device in accordance to EN 60715 by snapping it onto DIN-rail without tools (see figure 1):
1. Place the device with its DIN-rail guide on the top edge of the DIN-rail.
2. Press the device onto the DIN-rail [1] while simultaneously pulling on the latch (i) [2] until it
locks into place.
3. To ensure secure fastening on the DIN-rail, fit end clips on either side of the device (with a
block arrangement: on either side of the devices).
4.1.2 Removal from DIN-Rail
1. To remove (see figure 2) pull down the latch (i) [1] using a screwdriver or operating tool.
2. Tilt the device forward [2] and unhook it from the DIN rail.
4.2 Screw Mounting
The position and dimensions for the fastening clips are listed in the drilling template supplied with the
device.
1. Fit one fastening clip into each corresponding top and bottom snap-fit opening on the housing
(see figure 3).
2. Push down the fastening clip until it locks into place with an audible click.
3. Gently shake the fastening clip to verify that it is fitted securely.
1.1
1.2
2.1
2.2
1.1
2.1
Figure 3: Snap-fit openings for fastening clips – top/bottom view
Table 5: Legend for the “Snap-fit openings for fastening clips” figure
Pos.
Description
1.1
Snap-fit opening top; rear fastening (787-1226: 2 ×)
1.2
Snap-fit opening top; side fastening (only 787-1202 / 787-1212)
2.1
Snap-fit opening bottom; rear fastening (787-1226: 2 ×)
2.2
Snap-fit opening bottom; side fastening (only 787-1202 / 787-1212)
4. Fasten the device with the appropriate M4 screws (not included).
Observe the maximum torque of 2.9 Nm.
5 Wiring
Make sure that the
picoMAX
®
Female Connectors are mated properly!
Mismating the input female connector (b) into the output connector (c) may lead to a
hazardous voltage of 230 V on the output side.
Make sure that the female connector is properly mated!
Do not insert a tool into the ventilation slots!
Components inside the device may be damaged if the blade of an operating tool enters
the ventilation slots. This may lead to serious damage with a risk of injury caused by
malfunction, overheating or electric shock!
When using a screwdriver or an actuation tool, ensure correct positioning between the
locking latch and the female connector!
The following conductors can be inserted directly without tools:
• fine-stranded conductors with insulated ferrule, all cross sections
• fine-stranded conductors with uninsulated ferrule, cross section > 0.5 mm²/AWG 22
• solid conductors, cross section > 0.25 mm²/AWG 24