background image

9970-0966

s07870000_00000005 

V1.0.0 © 2016

WAGO Kontakttechnik GmbH & Co. KG

Hansastr. 27

D-32423 Minden

www.wago.com

En

Operating and Assembly instructions

Please keep!

Subject to design changes

Support:  Phone:  +49 (0) 571/8 87 - 5 55  /  Fax:  +49 (0) 571/8 87 - 85 55 

 

Mail: [email protected]

EPSITRON

®

 COMPACT Power

PE

L

N

DC+

DC+

DC -

DC -

DC power supply

787-1202 / 787-1212 /  

787-1216 / 787-1226

1  Safety Information

1.1  General

Do not work when devices are energized!

High  voltage can cause electric shock or burns. 

Switch off all power to the device prior to performing any installation, repair or main

-

tenance work.

Live parts are likely to be touched!

The party setting up the device is responsible for providing appropriate touch guards. 

 

The installation regulations must be observed for each individual application.

i

Only valid in conjunction with the device‘s manual!

These instructions are only applicable in conjunction with the device‘s manual!

 

This manual is available on the Internet at www.wago.com.
In addition, please observe the information provided on the device’s housing.

Please especially observe the following:

•  The device described in these instructions shall only be installed by a qualified electrician 

according to both DIN EN 50110-1/-2 and IEC 60364. 

•  Before startup, check the device for any damage that may have occurred during shipping. The 

device shall not be put into operation in the event of mechanical damage.

•  Ensure proper handling to protect device during shipping and handling. Parts must not be bent 

and electrical spacing must remain constant.

•  Only install this device in closed electrical service locations in accordance with 

DIN EN 50178. 

•  Only install this device in dry indoor rooms.

•  Do not install the devices on or in the vicinity of easily flammable materials.

•  Keep sufficient distance from adjacent components to avoid interfering with the cooling!

•  When used in accordance with EN 60335, the operator must provide a suitable mains isolator 

in the device supply line

Improper use and failure to follow these instructions for use will render the warranty or guarantee null 

and void.

1.2  Special Notes on Use as a DIN-Rail Built-in Installation Device

Ensure contact protection when used as a DIN-rail built-in installation device!

When used as a DIN-rail built-in installation device according to DIN 43880 (domestic 

installation), the electrical installer must provide appropriate contact protection. 
Only use the device 787-1202 or 787-1212 as a DIN-rail built-in installation device 

with the front panel fitted.

2  Technical Data

Table 1: Device

787-1202

787-1212

787-1216

787-1226

Dimensions (mm) W × H × D 

Depth including fastening clips (mm)

54 × 56 × 90

120

72 × 56 × 90

120

108 × 56 × 90 

120

144 × 56 × 90

120

Weight

210 g

270 g

415 g

510 g

Table 2: Wiring
Cross section 

0.2 mm² … 2.5 mm² / AWG 24 … 12

Strip length

9 mm … 10 mm / 0.35 in … 0.39 in

Select conductor cross sections as required for current load!

In the event of a fault, the output current of a power supply can be up to 2 × I

OUT

.

Only use conductor cross sections designed for this current load.

Table 3: Mounting

Mounting position 

(Other mounting positions on request)

Distances 

Top

Bottom Front

Rear

Left

Right

Vertical mounting (front panel front)

70 mm 70 mm 70 mm

---

0 mm

0 mm

Horizontal mounting (front panel top)

70 mm

---

70 mm 70 mm 20 mm 20 mm

Horizontal mounting (front panel bottom)

--- 

70 mm 70 mm 70 mm 20 mm 20 mm

3  View

Table 4: View (Example: 787-1226)

g

h

j

i

f

e

d

c

b

a

Pos. Assignment

a

Fastening clips for screw mounting  

(included)

b

picoMAX

®

 5 input (N L PE)

c

picoMAX

®

 5 output (+ + - -)

d

Potentiometer for setting the output  

voltage between 22 VDC … 26 VDC

e

LED indicator

LED green: Output voltage present

f

Front panel 

787-1202 / 787-1212:  removable

787-1216 / 787-1226:  not removable

g

Type plate

h

Ventilation slots

i

Mount/removal latch on a DIN-rail

j

Slide switch for setting the input voltage 

range (only 787-1226):

110 V 

100 VAC … 120 VAC

230 V 

200 VAC … 240 VAC

4  Mounting

Install the device vertically to ensure proper heat dissipation (ventilation slots above and below). 
The following values should not be exceeded when installing with the front panel at the top or 

 

bottom: 

•  Output power: 

50 % (787-1202 / 787-1212 / 787-1216)

 

 

40 % (787-1226)

•  Ambient temperature: 

55 °C

Other mounting positions should only be used at one‘s own risk! 

Avoid electrostatic discharge!

The devices are  equipped with electronic components that you may destroy by 

electrostatic discharge when you touch. Please observe the safety precautions against 

electrostatic discharge in accordance with DIN EN 61340-5-1/-3

Pay attention while 

handling the devices to good grounding of the environment (persons, job and packing).

4.1  DIN 35 Rail

1.

2.

2.

1.

Figure 1: Mounting   

Figure 2: Removal

4.1.1  DIN-Rail Mounting

Install the device in accordance to EN 60715 by snapping it onto DIN-rail without tools (see figure 1):

1.  Place the device with its DIN-rail guide on the top edge of the DIN-rail. 

2.  Press the device onto the DIN-rail [1] while simultaneously pulling on the latch (i) [2] until it 

locks into place.

3.  To ensure secure fastening on the DIN-rail, fit end clips on either side of the device (with a 

block arrangement: on either side of the devices).

4.1.2  Removal from DIN-Rail

1.  To remove (see figure 2) pull down the latch (i) [1] using a screwdriver or operating tool.

2.  Tilt the device forward [2] and unhook it from the DIN rail.

4.2  Screw Mounting

The position and dimensions for the fastening clips are listed in the drilling template supplied with the 

device.

1.  Fit one fastening clip into each corresponding top and bottom snap-fit opening on the housing 

(see figure 3). 

2.  Push down the fastening clip until it locks into place with an audible click. 

3.  Gently shake the fastening clip to verify that it is fitted securely.

1.1

1.2

  

 

 

2.1

2.2

1.1

  

 

2.1

Figure 3: Snap-fit openings for fastening clips – top/bottom view

Table 5: Legend for the “Snap-fit openings for fastening clips” figure

Pos.

Description

1.1

Snap-fit opening top; rear fastening (787-1226: 2 ×)

1.2

Snap-fit opening top; side fastening (only 787-1202 / 787-1212)

2.1

Snap-fit opening bottom; rear fastening (787-1226: 2 ×)

2.2

Snap-fit opening bottom; side fastening (only 787-1202 / 787-1212)

4.  Fasten the device with the appropriate M4 screws (not included). 

 

Observe the maximum torque of 2.9 Nm.

5  Wiring

Make sure that the 

picoMAX

®

 Female Connectors are mated properly!

Mismating the input female connector (b) into the output connector (c) may lead to a 

 

hazardous voltage of 230 V on the output side.
Make sure that the female connector is properly mated!

Do not insert a tool into the ventilation slots!

Components inside the device may be damaged if the blade of an operating tool enters 

the ventilation slots. This may lead to serious damage with a risk of injury caused by 

malfunction, overheating or electric shock!
When using a screwdriver or an actuation tool, ensure correct positioning between the 

locking latch and the female connector!

The following conductors can be inserted directly without tools:

•  fine-stranded conductors with insulated ferrule, all cross sections

•  fine-stranded conductors with uninsulated ferrule, cross section > 0.5 mm²/AWG 22 

•  solid conductors, cross section > 0.25 mm²/AWG 24