WAGO-SPEEDWAY 767
Parameterizing
55
767-6402 4 AI RTD
Manual
Version 3.1.0
Table 27: Overview of adjustable parameters for the analog inputs
Parameter
Description
Measuring range
underflow
If there is a limit value overrun or underrun, the corresponding
diagnostic is displayed here.
If the "Simulation" parameter is activated, you can simulate the
corresponding diagnostic state by selecting this parameter.
Measuring range
overflow
User limit underflow
User limit overflow
Extended parameters
Integration time
Here you can set the integration time of the AD converter.
Default setting: 60 ms.
This integration time is ideal for suppressing an interference frequency
of 50 or 60 Hz.
The following options are available:
2 ms
4 ms
8 ms
16.7 ms
20 ms
30 ms
60 ms
*
120 ms
Type of sensor
connection
You have the following options:
- Switched off
- 2-wire
- 3-wire
*
- 4-wire
Offset for 2-wire
compensation
Here you can enter the line resistance of the supply line to the sensor.
This is only necessary for the 2-wire connection type.
*
Default setting