WAGO-SPEEDWAY 767 

Service 

87 

767-5803 8DIO 24V DC 0,5A (8xM12) 

 

 

Manual 

 

Version 1.1.0  

 

Pos: 45 /All e Seri en (Allgemei ne Module)/Ü berschriften für alle Serien/Ser vice ( Wartung)Ser vice - Ü berschrift 1 @ 4\mod_1241771948421_21.docx @ 32830 @ 1 @ 1 

 

11 

Service 

Pos: 46 /Serie 767 ( WAGO-SPEED WAY)/Ser vice/I/O-M odule/Ser vice 767- xxxx allgemein 1 @ 7\mod_1267790134757_21.docx  @  51798 @  @ 1 

 

This section contains information on maintenance and service. 

Pos: 47 /Serie 767 ( WAGO-SPEED WAY)/Ser vice/I/O-M odule/Ser vice 767- xxxx Firmwareupdate @ 8\mod_1278567931191_21.docx @ 59308 @ 2 @ 1 

 

11.1  Updating the Firmware 

The firmware for the module can be updated. This takes place via the USB 

connection of a fieldbus coupler. Additional information can be found in the 

fieldbus manuals in section "Updating the Firmware". 

Pos: 48 /Serie 767 ( WAGO-SPEED WAY)/Ser vice/I/O-M odule/Ser vice 767- xxxx allgemein 2 @ 5\mod_1249468812328_21.docx @ 40442 @ 23 @ 1 

 

11.2  Replacing the Module 

To replace a module, e.g., to change variants, proceed as described follow. 

11.2.1  Disconnecting the Cables 

Before removing the connectors, clean the module to ensure that no dirt or other 

material comes in contact with the connections. This can lead to damage of the 

contacts. 

To unplug the cables, proceed as follows: 

1.   Disconnect the power supply from those devices on which you have 

mounted the module. 

Pos: 49 /Serie 767 ( WAGO-SPEED WAY)/Wichtige Erläuterungen/Sicherheitshinweise/Vorsicht/Vorsicht: H eiße Anschlussbuchsen @ 8\mod_1278308217203_21.docx @  58913 @  @ 1 

 

 

 

 

Hot connection sockets! 

Even when taking into account derating, high surface temperatures on the metallic 

connection sockets and on the enclosure can arise during operation. If the 767 

Series component has been in operation, allow it to cool off before moving it. 

 

Pos: 50 /Serie 767 ( WAGO-SPEED WAY)/Ser vice/I/O-M odule/Ser vice 767- xxxx allgemein 2.1 @ 8\mod_1278568242751_21.docx  @  59311 @   @ 1 

 

2.   Unscrew all screw connections and remove the cables. 

Pos: 51 /D okumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810  @   @  1 

 

 

 

Summary of Contents for 767-5803

Page 1: ...0 docx 64941 1 WAGO SPEEDWAY 767 Manual 767 5803 8DIO 24V DC 0 5A 8xM12 Digital Input Output Module DC 24 V 0 5 A Version 1 1 0 Pos 3 Alle Serien Allgemeine M odul e Hinweise zur Dokumentation Impress...

Page 2: ...71 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never be fully excluded we always app...

Page 3: ...n Operation 14 3 Device Description 15 3 1 Connectors 16 3 2 Marking Possibilities and Fastening 17 3 3 Display Elements 18 3 4 Labeling 19 3 5 Schematic Diagram 21 3 6 Dimensions 22 3 7 Technical Dat...

Page 4: ...Cable 49 6 Commissioning 51 7 Parameterizing 52 7 1 Electronic Type Label 54 7 2 Diagnostic Overview 55 7 2 1 Input and Output Parameters 57 7 2 2 DO Module Mode 58 7 2 3 DI Module Mode 60 7 2 4 DIO M...

Page 5: ...ting the Firmware 87 11 2 Replacing the Module 87 11 2 1 Disconnecting the Cables 87 11 2 2 Removing the Module from Your System 88 11 2 3 Removing the Module from the Carrier Rail 88 11 2 4 Removing...

Page 6: ...t www wago com There you will find information regarding supply layout etc Pos 11 All e Seri en Allgemei ne Module Hi nweise zur D okumentati on Hinweise Hinweis Dokumentation aufbewahr en 4 mod_12379...

Page 7: ...erien Allgemei ne Module Wichtige Erl uterungen Sicherheits und sonstige Hinweise Vorsicht Vorsicht _War nung vor Personensch den allgemein_ Erl uterung 13 mod_1343310028762_21 docx 101038 1 Personal...

Page 8: ...4V DC 0 5A 8xM12 Manual Version 1 1 0 Additional Information Refers to additional information which is not an integral part of this documentation e g the Internet Pos 13 5 Dokumentation allgemei n Gli...

Page 9: ...21714 2 1 1 5 Font Conventions Table 2 Font Conventions Font Type Indicates italic Names of paths and data files are marked in italic type e g C Program Files WAGO Software Menu Menu items are marked...

Page 10: ...llgemei ne Module Wichtige Erl uterungen nderungsvor behalt berschrift 3 und Inhalt 3 mod_1221060036484_21 docx 21720 3 1 2 1 1 Subject to Changes WAGO Kontakttechnik GmbH Co KG reserves the right to...

Page 11: ...ule may only be operated in combination with components of the WAGO SPEEDWAY 767 Series The module was developed for applications requiring IP 67 NEMA type 6 6P protection Pos 16 9 Serie 767 WAGO SPEE...

Page 12: ...ies component and the overall power consumption for all 767 components Neither of these values shall exceed 4 A since an increase in current causes the contacts to overheat and damages the 767 Series...

Page 13: ...rds for EMC suitable installations For the power supply and for the S BUS use only pre assembled WAGO system cables so the specified characteristics of the technical data can be achieved Pos 16 19 Ser...

Page 14: ...stem to protective earth PE and Pos 16 23 Serie 767 WAGO SPEED WAY Wichtige Erl uter ung en I O Modul Hinweise zum Betri eb 767 I O Teil 2 5 mod_1248180225875_21 docx 38755 1 Ensure that the cable rou...

Page 15: ...er channel This mode combines inputs and outputs on one module By default all channels are configured as digital inputs DIO mode 1 counter Combined operation of digital inputs and outputs with a count...

Page 16: ...ts 2 S BUS output M12 socket B coded For transmitting S BUS data to the next 767 Series components or to the S BUS terminator Pos 18 7 Serie 767 WAGO SPEED WAY Ger tebeschrei bung Anschl sse I O Modul...

Page 17: ...767 WAGO SPEED WAY Ger tebeschr eibung Befestigung I O Module Legende zu Beschriftung und Befestigung 767 xxxx 5 mod_1249475777546_21 docx 40514 1 Table 4 Legend for figure Marking possibilities and...

Page 18: ...e 5 Legend for figure Display elements Position LED Color Meaning 15 SB Green red orange S BUS status 16 F Red Diagnostic information Pos 18 16 Serie 767 WAGO SPEED WAY Ger tebeschr eibung Anzeigeel e...

Page 19: ...767 WAGO SPEEDWAY Ger tebeschr eibung Bedr uckung I O M odul e Legende zur Bedr uckung 767 5803 DIO 13 mod_1350636358318_21 docx 104940 1 Table 6 Legend for figure Labeling Position Description 30 Man...

Page 20: ...he module Pos 18 20 Serie 767 WAGO SPEED WAY Ger tebeschr eibung Bedr uckung I O M odul e Bedruckung sei tlich Legende 9 mod_1286969974465_21 docx 65601 1 Table 7 Description of manufacturing number A...

Page 21: ...of the power supply connections as well as the digital inputs and outputs of the modules see also chapters Connecting the Supply Cable and Connecting the Sensor Actuator Cable Please note that the po...

Page 22: ...sungen berschrift 2 5 mod_1248869612468_21 docx 39441 2 1 3 6 Dimensions Pos 18 27 Serie 767 WAGO SPEED WAY Ger tebeschr eibung Abmessungen I O M odule Abmessungen 767 xxxx_IO_8xM 12 Bild 11 mod_13173...

Page 23: ...al Data General Information Width 50 mm Height 35 7 mm Lowness 170 mm Pos 18 32 Serie 767 WAGO SPEED WAY Ger tebeschr eibung Technische Daten I O M odule Ger tedaten_2_8xM12 11 mod_1317819571683_21 do...

Page 24: ...t filter Hardware 60 s Software parametrizable Input characteristic Type 2 acc to IEC 61131 2 Signal voltage 0 Signal voltage 1 DC 3 V 5 V DC 11 V 30 V Input circuit high side switching Input voltage...

Page 25: ...7 0 mA 30 V 7 1 mA 3 7 6 Outputs Table 13 Technical data Outputs No of outputs 8 Connection type M12 connectors A coded 4 poles Wire connection 2 or 3 wire Output voltage UA Output current per channel...

Page 26: ...ower boost for redundant actuation of a load Type of protective circuit External protection e g recovery diodes Output resistance 0 4 Wrong diagnostics may occur at high switching frequencies with red...

Page 27: ...put module Input and output module 1 counter Input and output module 2 counter Input filter per channel 0 1 0 5 3 15 20 ms Filter off Inversion per channel on off Substitute value strategy per channel...

Page 28: ...r from 0 65535 Disabled Enabled Counter start value limit value Value 0 65535 Set start value limit value Count direction forward Set counter value to 0 Limit value is to be specified Count direction...

Page 29: ...Depends on operating mode 3 7 14 Indicators Table 21 Technical Data Indicators SB S BUS status LED green red orange F Error status LED red 0 7 Input and output signal status LED yellow 0 7 Output diag...

Page 30: ...cU Lus UL508 3 mod_1224055013140_0 docx 24020 1 CULUS UL508 Pos 18 36 3 3 D okumentati on allgemein Gli ederungsel emente Leerzeil e 3 mod_1224662755687_0 docx 24460 1 Pos 18 36 4 Serie 767 WAGO SPEED...

Page 31: ...ective 94 9 EC Pos 18 38 7 Alle Serien Allgemeine M odul e Nor men und Richtlini en Ex i Nor men Explosionsf hig e Atmosph r e EN 60079 0 14 mod_1360841627885_21 docx 111880 1 Explosive atmosphere EN...

Page 32: ...767 xxxx allgemei n_1 5 mod_1249028727125_21 docx 39643 2 1 4 1 Information on Mounting The following information shall always be observed Disconnect the power supply from the system before you start...

Page 33: ...21 docx 196008 1 Any mounting position is possible Ensure a safe mounting position In explosion hazardous environments no increased mechanical loads must be present at the installation location If sho...

Page 34: ...anuals in the Accessories section Select the manual appropriate to the fieldbus you are using Carrier rail adapter including fixing screws and perforated or imperforated carrier rails DIN rail 35 x 7...

Page 35: ...ll cable without problems Pos 21 11 Serie 767 WAGO SPEED WAY Wichtige Erl uter ung en Sicherheitshinweise Hinweis Hi nweis 767 xxxx Distanzst ck 8 mod_1279025151416_21 docx 59810 1 Direct Mounting We...

Page 36: ...ail Adapter to the Module A carrier rail adapter is required to mount the module on carrier rails Screw together the module and carrier rail adapter using the M4 threaded screws provided as shown in t...

Page 37: ...the edge of the carrier rail 51 with the two notches 50 3 Press the undersurface against the lower carrier rail edge until the latch 52 locks in place Rail Adapter for 767 modules with 8xM12 connectio...

Page 38: ...also have the option to fasten it to a profile rail using the profile adapter and nuts provided that this mounting type is supported by your system You are to supply the necessary nuts Screw together...

Page 39: ...o nuts are required with one screw each length of screw threads must be compatible with your system 1 Disconnect the power supply from those devices on which you wish to mount the module 2 Insert the...

Page 40: ...width 3mm into the small opening under the marking strip cover 12 and lever it up 2 Remove the marking strip cover 3 Mark the marking strip with a waterproof pen 4 Reinsert the marking strip cover and...

Page 41: ...ed on the spacer for cable ties 1 Disconnect the power supply from those devices on which you wish to mount the module 2 The spacer can only be inserted into the appropriate openings of the module fro...

Page 42: ...67 component connected with a spacer can be attached and screwed on to the preceding component due to the mounting direction The last 767 component is fastened without a spacer Pos 21 33 Serie 767 WAG...

Page 43: ...can be found in the corresponding data sheet which is available from www wago com Pos 23 5 Serie 767 WAGO SPEED WAY Wichtige Erl uterungen Sicherheitshinweise Achtung Achtung Offene Anschl sse 8 mod_...

Page 44: ...diuses of the WAGO system cable For more information see the technical data at www wago com When laying all cable ensure that you do not lay it in shear areas of moving machine parts Observe the corre...

Page 45: ...r communication between a fieldbus coupler and the connected 767 Series components Requirement A WAGO S BUS cable pre assembled on both ends is readily available to you This is necessary for optimal s...

Page 46: ...ave been connected to the fieldbus coupler connect the S BUS cables S1 S2 to the associated IN and OUT connections as shown in the following figure 3 Tighten the plugs and sockets using the knurled he...

Page 47: ...kontakte 8 mod_1278308653219_21 docx 58916 1 The highest current carrying capacity of the supply contacts is 4 A Always observe the maximum current carrying capacity per supply line ULS UA for each 76...

Page 48: ...connected to the fieldbus coupler connect the power supply transmission cable K1 K2 with the associated IN and OUT connections as shown in the following figure 3 Tighten the plugs and sockets using t...

Page 49: ...gnment Channel Connection Counter 1 X1 1 2 X2 3 X3 4 X4 5 X5 2 6 X6 7 X7 8 X8 Pos 23 23 Serie 767 WAGO SPEED WAY Wichtige Erl uter ung en Sicherheitshinweise Achtung Achtung H chste Strombel astbar be...

Page 50: ...es on which you have mounted the module 2 Insert the plug of the sensor or actuator cable into the socket of a digital input output 3 of the module and tighten it using the knurled head screw 3 Screw...

Page 51: ...which must be ordered separately in order to maintain the IP67 degree of protection See section Accessories of the fieldbus coupler controller manual Pos 27 Serie 767 WAGO SPEED WAY In Betrieb nehmen...

Page 52: ...angerous state and personnel and machines could be at risk Before changing the parameters ensure that the machine components are in a safe and defined state and switch off the higher level controller...

Page 53: ...rites the modified values to the module Close Online and offline mode Closes the parameterization user interface DTM Apply Offline mode only Applies the entries in the project Please note that the pro...

Page 54: ...turer Release index FW HW FL FW Actual firmware release index When updating the firmware please note that the firmware release index may not be conformed to the printed firmware release index on the s...

Page 55: ...from the actual module Pos 30 7 Serie 767 WAGO SPEED WAY Par ametrieren I O M odule Parametri erung 767 xxxx Di agnose bersicht_2 7 mod_1265811272140_21 docx 50279 1 Table 29 Diagnostics setup Paramet...

Page 56: ...module the outputs are disabled and a corresponding diagnostic transmitted to the fieldbus coupler The module F LED illuminates Pos 30 10 Serie 767 WAGO SPEED WAY Parametrier en I O Module Parametrier...

Page 57: ...operated When using e g DIO mode each connection in the DTM can be configured as a digital input or output Table 32 Overview of operating modes Parameter Description Operating type DO module Operatio...

Page 58: ...ed in process image Checkbox selected Output signal is released in an inverted manner as indicated in process image Substitute strategy This releases the substitute value or the last output value in c...

Page 59: ...ty supports Information about diagnostic acknowledgement When using fieldbus couplers that do not support the diagnostic acknowledgement disabled outputs may remain OFF Restart delay actuator Time in...

Page 60: ...rently pending input signal here Checkbox unselected Input signal is reproduced in the process image in the same manner as the input Checkbox selected Input signal is reproduced in the process image i...

Page 61: ...e module inputs see section Control of the Counter via Inputs and Outputs No If you select this option the counter is controlled by the process data control byte See section Control Byte State Gate Th...

Page 62: ...ta control byte or the DTM Reset limit status The limit value status is reset by enabling this field If the Switching Output parameter is selected it is also reset Auto reset upon limit If you enable...

Page 63: ...r en I O Module Parametrier ung 767 38xx 5xxx 6401 7401 Param der Fel dversorgung 5 mod_1249379780656_21 docx 40285 2 1 7 4 Parameters of Field Supply Table 37 Overview of adjustable parameters for th...

Page 64: ...replaced due to a defect you do not need to reconfigure the new I O module The stored parameters are automatically transferred to the new I O module Detailed information on this procedure can be found...

Page 65: ...21 docx 40223 1 The process images for the module listed in the following sections describe the data length on the S BUS system bus The implementation of the S BUS process images onto the respective f...

Page 66: ...35 Serie 767 WAGO SPEED WAY Wichtige Erl uterungen Sicherheitshinweise Hi nweis Hinweis Prozessabbil d 767 5xxx 8 mod_1278504041994_21 docx 59260 1 Diagnostic Actuator short circuit overload The Actu...

Page 67: ...nfigure synchronous diagnostic data for the I O module the process image has a size of 2 bytes The byte configuration is as follow Table 38 DO input data in the process image Byte 0 7 0 Diagnostic mes...

Page 68: ...ut data in the process image Byte 0 7 0 Digital outputs process data 1B Input value True Byte 1 7 0 Diagnostic confirmation 1B Overtemperature on channel 1 conf 1B Overtemperature on channel 2 conf 1B...

Page 69: ...If you configure synchronous diagnostic data for the I O module the process image has a size of 3 bytes The byte configuration is as follows Table 40 DI input data in the process image Byte 0 7 0 Digi...

Page 70: ...gure a synchronous diagnostic confirmation of the I O module the process image has a size of 2 bytes The diagnostic confirmation is structured as follows Table 41 DI output data in the process image B...

Page 71: ...lows Table 42 DIO input data in the process image Byte 0 7 0 Digital inputs process data 1B Input value True State of the outputs is also displayed Byte 1 7 0 Diagnostic message 1B Overtemperature on...

Page 72: ...data in the process image Byte 0 7 0 Digital outputs process data 1B Input value True Byte 1 7 0 Diagnostic confirmation 1B Overtemperature on channel 1 conf 1B Overtemperature on channel 2 confirmed...

Page 73: ...r input data in the process image Byte 0 7 0 Digital inputs process data 1B Input value True State of the outputs is also displayed Byte 1 7 0 Counter status 1B See section Counter Function Byte 2 15...

Page 74: ...oltage ULS 1B Undervoltage UA Not assigned always 0 8 4 2 Output Data The image for the process data which are transmitted by the fieldbus coupler to the I O module has a size of 4 bytes If you config...

Page 75: ...See section Counter Function Byte 4 7 0 Diagnostic confirmation 1B Overtemperature on channel 1 conf 1B Overtemperature on channel 2 conf 1B Overtemperature on channel 3 confirmed 1B Overtemperature o...

Page 76: ...ze of 8 bytes The byte configuration is as follows Table 46 DIO 2 counters input data in the process image Byte 0 7 0 Digital inputs process data 1B Input value True State of the outputs is also displ...

Page 77: ...emperature on channel 7 1B Overtemperature on channel 8 Byte 7 7 0 Diagnostic message 1B Short circuit overload field supply always 0 1B Undervoltage ULS 1B Undervoltage UA Not assigned always 0 8 5 2...

Page 78: ...confirmation 1B Overtemperature on channel 1 conf 1B Overtemperature on channel 2 conf 1B Overtemperature on channel 3 confirmed 1B Overtemperature on channel 4 confirmed 1B Overtemperature on channel...

Page 79: ...trol byte by default This bit must be enabled to use the counter functions see section Control Byte The counting takes place edge controlled that is the counter status is incremented or decremented wh...

Page 80: ...module switch these on via DTMs using WAGOframe or another FDT DTM framework application You can find the necessary DTMs at wago com This configuration is also possible with some fieldbus systems e g...

Page 81: ...trolled via a physical input 0B Reset the gate counter is blocked 1B Set the gate counter is released Count direction Control of the count direction if this is not controlled via an input 0B up 1B dow...

Page 82: ...s image which is defined as follows Table 50 Status byte 7 0 Status byte counter 1 2 Gate status counter 1 0B inactive 1B active Count direction counter 1 0B up counter 1B down counter Limit value sta...

Page 83: ...the control mode bit of the status byte is then read via the process data input data When setting the start or limit value the value must remain in the output process image after resetting the control...

Page 84: ...ics Use the diagnostic overview section Parameterizing Diagnostic Overview to disable specific diagnostics see F and I O LED In this case the corresponding LED is disabled off Pos 43 3 Serie 767 WAGO...

Page 85: ...eing updated All 767 Series components are being updated by the fieldbus coupler within the node Orange flashing 4 Hz The module is attempting to establish communication with the fieldbus coupler Chec...

Page 86: ...ad can only be diagnosed if the output is switched on If you set the time of the parameter Restart delay actuator section Parameterizing Parameters of outputs to 0 ms the I O LED appears yellow rather...

Page 87: ...ing the Module To replace a module e g to change variants proceed as described follow 11 2 1 Disconnecting the Cables Before removing the connectors clean the module to ensure that no dirt or other ma...

Page 88: ...moving the Module from the Carrier Rail In order to keep the representation unambiguous the carrier rail adapter in the following figure B C is shown without module If the module is mounted on a carri...

Page 89: ...emove the module from the profile rail of your system 3 Unscrew the screws that connect the module with the profile adapter 11 2 5 Connecting the Module To connect the module proceed as described in S...

Page 90: ...attribute path into a fieldbus specific message The following diagnostic codes can be generated by the module Table 54 Diagnostics of the module Diagnostic Message Attribute Path Classification C I A...

Page 91: ...xemplary 37 Figure 11 Fastening to the profile adapter 38 Figure 12 Replacing the marking spaces 40 Figure 13 Attaching a spacer to a module 41 Figure 14 Attaching another module with a spacer 42 Figu...

Page 92: ...data Isolation 29 Table 23 S BUS connection assignment 45 Table 24 Supply connection assignment 47 Table 25 Digital inputs outputs connection assignment 49 Table 26 Counter Assignment of channels for...

Page 93: ...81 Table 50 Status byte 82 Table 51 Example of controlling two counters via control byte 83 Table 52 Operating messages 1 84 Table 53 Operating messages 2 86 Table 54 Diagnostics of the module 90 Tabl...

Page 94: ...x 21123 1 Pos 66 D okumentation allgemei n Einband Einband H andbuch R ckseite 2015 9 mod_1285229376516_21 docx 64944 1 WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 324...

Reviews: