76
Appendix
WAGO-SPEEDWAY 767
767-4803/000-800 8DO 24V DC 2.0A IF (8xM8)
Manual
Version 1.1.0
Pos: 61 /All e Seri en (Allgemei ne Module)/Ü berschriften für alle Serien/Anhang - Z ubehör Anhang - Ü berschrift 1 @ 4\mod_1239874070437_21.docx @ 30560 @ 1 @ 1
12
Appendix
Pos: 62 /Serie 767 ( WAGO-SPEED WAY)/Anhang/I/O-M odule/Anhang 767-48xx Di agnoseinfor mation @ 5\mod_1249471902718_21.docx @ 40474 @ 2 @ 1
12.1 Diagnostic Information
Some fieldbus couplers display the error code in the form of an attribute path
(CIA), through which diagnostics are clearly assigned. Other fieldbus couplers
(e.g., PROFINET I/O or PROFIBUS DP) convert the attribute path into a
fieldbus-specific message.
The following diagnostic codes can be generated by the module:
Table 32: Diagnostics of the module
Diagnostic Message
Attribute Path
Classification
C
I
A
Low voltage U
LS
(sensor supply)
50
1
128 Diagnostic alarm
Low voltage U
A
(actuator supply)
50
1
129 Diagnostic alarm
Table 33: Diagnostics of the individual channels of the module
Diagnostic Message
Attribute Path
Classification
C
I
A
Actuator short circuit/overload
This function is only enabled when the
actuator output is switched on.
9 Channel
(1 … 8) 128 Diagnostic alarm
Actuator open load (line break)
This function is only enabled when the
actuator output is switched off.
9 Channel
(1 … 8) 129 Diagnostic alarm
Overtemperature
This function is only enabled when the
actuator output is switched on.
9 Channel
(1 … 8) 130 Diagnostic alarm
Use the "Diagnostic Overview" to disable specific diagnostics.
=== Ende der Liste für T extmar ke Inhalt_mitte ===