24
Device Description
WAGO-SPEEDWAY 767
767-4801/000-800 8DO 24V DC 0.5A IF (8xM8)
Manual
Version 1.1.0
3.7.5
Information on Selecting the Actuator
Table 12: Technical data – Information on Selecting the Actuator
Delay time HW
from 0 to 1 (0 – 90 %)
from 1 to 0 (0 - 90 %)
Typically 75 µs (resistive load)
Typically 270 µs (resistive load)
Rise time
from 0 to 1
Fall time
from 1 to 0
Typically 40 µs (resistive load)
Typically 50 µs (resistive load)
Cable length, unshielded
≤ 30 m
Protection against reverse voltages 0,5 A
Type of load
Inductive, resistive loads and lamps
Switching frequency
Inductive load, approx. 20 Hz
Resistive load, approx. 500 Hz
Lamp load, approx. 500 Hz
Recommended minimum load
50 mA
*
Parallel connection of 2 outputs
For power boost
For redundant actuation of a load
Type of protective circuit
External protection (e.g., recovery diodes)
Output resistance
< 0.4 Ω
*
Wrong diagnostics may occur at high switching frequencies with reduced load.
3.7.6
Influence of Operating States on Output
Table 13: Technical data – Influence of Operating States on Output
CPU stop of PLC
Acc. to substitute value strategy
Break of field bus
Acc. to substitute value strategy
Break of S-BUS
0 V status
Supply voltage under rated voltage
tolerance
0 V status
Interruption of supply voltage
0 V status
Output operation
Non-latching
Overload behavior
Automatic restart