765-4102/0100-0000
Commissioning
Product manual | Version: 2.1.0
73
8PORT IOL-B FLD PN DC 24V 2.0A
Table 43: Possible Values of “State” (Port Status Information)
Value
Port Status
Description
3
Preoperate
The product is ready for communi-
cation
4
Operate
The product is communicating
5
DI CQ
The port is in digital input mode
6
DO CQ
The port is in digital output mode
7
Reserved
Reserved
8
Reserved
Reserved
9
Incorrect Cycle Time
The cycle time according to the con-
figuration does not correspond to
the connected product
254
Port Power Off
The port voltage is switched off
255
Not Available
The port is not available
10.2.2.3.5 Quality
This shows the
Port Quality Info
, including information on the validity of the process data
for input and output (separately). The content is binary coded.
Table 44: Meaning of the Individual Bits
Bits of Port Quality Info
Description
Bit 0
0 = input process data valid
1 = input process data invalid
Bit 1
0 = output process data valid
1 = output process data invalid
Bit 2 to bit 7
Reserved
10.2.2.3.6 Revision ID
This shows the revision ID of the connected product.
A value of 0 means: no product connected.
All other values must be interpreted as the revision ID of the connected product.
10.2.2.3.7 Baud Rate
If an IO-Link product is connected to the port, its data transmission rate appears here. For
IO-Link, the transmission rate of the communication between the port and a connected
product can have the following values:
• 4.8 kbit/s (COM1)
• 38.4 kbit/s (COM2)
• 230.4 kbit/s (COM3)
If no IO-Link product is connected to the port, the text
Not connected
appears here.
10.2.2.3.8 Cycle Time
The cycle time of the master is bit-coded as follows:
• Bits 0 ... 5 specify a whole-number multiplier between 0 and 63.
• Bits 6 ... 7 specify the calculation formula to use according to the following table:
Table 45: Cycle Time of the Master
Bits 6 ... 7
Calculation Formula
0
Multiplier * 0.1 ms