WAGO-TO-PASS® 761 

Important Notes 

13 

761-112 Telecontrol Module Compact, Web 

 

 

Manual 

 

Version 2.0.0  

 

 

 

 

Please note the following information about FCC Part 15! 
 
FCC Part 15.19

  

This device complies with Part 15 of the FCC Rules.  
Operation is subject to the following conditions: 
1. this device may not cause harmful interference, and 
2. this device must accept any interference received, including interference that 
may cause undesired operation.  
 

FCC Part 15.21

  

Modifications not expressly approved by this company could void the user's 
authority to operate the equipment..  
 

Installation by qualified electrician only

 

The 

TO-PASS

®

 telecontrol module must be operated with Antenna 758-0963.  

The antenna gain main not exceed 3 dBi.  
Only qualified staff can install and maintain the 

TO-PASS

®

 remote module and its 

antenna. The transmitted must be off when working on or nearer to the antenna 
than specified below.  
 

HF-Exposition

  

The external antenna operated with the 

TO-PASS

®

 remote module must be at least 

20 cm away from people. The antenna may not be positioned, so that it works in 
conjunction with any other antenna or transmitter. 

 

 

 

 

 

Hot surface! 

The surface of the housing can become hot during operation. If the device was 
operated at high ambient temperatures, allow it to cool off before touching it. 

 

 

 

 

 

Do not reverse the polarity of connection lines! 

Avoid reverse polarity of data and power supply lines, as this may damage the 
devices involved. 

 

 

 

 

 

Replace defective or damaged devices! 

Replace defective or damaged device/module (e.g., in the event of deformed 
contacts), since the long-term functionality of device/module involved can no 
longer be ensured. 

 

 

Summary of Contents for 761-112

Page 1: ...Manual WAGO TO PASS 761 Telecontrol Module Compact Web 761 112 Telecontrol module for fault detection indication monitoring and remote control Version 2 0 0...

Page 2: ...0 571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never be fu...

Page 3: ...n Source GPL 11 2 4 Block Rounding for GPRS Connections 11 2 5 Safety Advice Precautions 12 3 Device Description 15 3 1 Scope of Delivery 15 3 2 Use 15 3 3 View 17 3 4 Connectors 18 3 4 1 Antenna 18 3...

Page 4: ...6 7 Configuring Inputs and Outputs 48 6 8 Digital Inputs 48 6 9 Multiplex Input 52 6 10 Multiplex Settings 53 6 10 1 1 Multiplex Alarm Text 54 6 10 2 Digital Outputs 55 6 11 Configuring Error Detector...

Page 5: ...ample of Value Script FW 2 31 Extended 88 10 2 1 1 Value Script FW 2 33 Counter Inputs 89 10 2 1 2 Example of Value Script FW 2 33 Counter Inputs 91 10 2 2 Logger Script 92 10 2 2 1 Logger Script Stan...

Page 6: ...ions are included if applicable 1 1 Validity of this Documentation This documentation is only applicable to the telecontrol module 761 112 Telecontrol Module Compact Web 1 2 Copyright This Manual incl...

Page 7: ...tes a moderate risk potentially hazardous situation which if not avoided could result in death or serious injury Personal Injury Indicates a low risk potentially hazardous situation which if not avoid...

Page 8: ...s Documentation WAGO TO PASS 761 761 112 Telecontrol Module Compact Web Manual Version 2 0 0 Additional Information Refers to additional information which is not an integral part of this documentation...

Page 9: ...ta files are marked in italic type e g C Programme WAGO I O CHECK Menu Menu items are marked in bold letters e g Save A greater than sign between two names means the selection of a menu item from a me...

Page 10: ...utomation The specialists must be familiar with the current norms and guidelines for the devices and automated environments All changes to the controller should always be carried out by qualified pers...

Page 11: ...n Source GPL The TO PASS Compact telecontrol module firmware contains Open Source software under GPL According to Section 3b of GPL we offer you the source code You can obtain the source code with lic...

Page 12: ...tion repair or maintenance work Installation only in appropriate housings cabinets or in electrical operation rooms TO PASS telecontrol modules are exposed operating equipment They may only be assembl...

Page 13: ...nly qualified staff can install and maintain the TO PASS remote module and its antenna The transmitted must be off when working on or nearer to the antenna than specified below HF Exposition The exter...

Page 14: ...an enclosure being resistant to the above mentioned materials Clean tools and materials are imperative for handling devices modules Cleaning only with permitted materials Clean soiled contacts using o...

Page 15: ...e connection of signals from plants transmission preparation of values for the operator TO PASS telecontrol modules 761 112 may be used as fault indicator remote data request system permanent on line...

Page 16: ...ion Standard Extended Extended Parameterizable Time request script Not implemented Not implemented Not implemented Implemented Counter inputs Not supported Not supported Not supported Supported Delay...

Page 17: ...761 112 Telecontrol Module Compact Web Manual Version 2 0 0 3 3 View Figure 1 Front view Position Description 1 SIM Card insert 2 Antenna connection 3 Statusindication 4 PC interface 5 Connecting term...

Page 18: ...ors 3 4 1 Antenna The screw connector SMA socket for the GSM antenna is located at the top of the housing Figure 2 Antenna connection Observe the maximum length of the antenna cable The total length o...

Page 19: ...e LPS requirements per DIN EN 60950 1 Table 4 Terminal assignment for operating voltage Figure 3 Terminal assignment for operating voltage Connection Short name Designation 1 2 Uv Operating voltage DC...

Page 20: ...nstructively no direct conduction connection between the cabinet frame or machine parts and the carrier rail Here the earth ground must be set up via an electrical conductor accordingly valid national...

Page 21: ...achieve this connect the shield over a large surface area e g WAGO shield connecting system This is especially recommended for large scale systems where equalizing current or high impulse type current...

Page 22: ...AGO Shield Connecting System The WAGO shield connecting system consists of shield clamping saddles busbars and various mounting carriers to enable a wide variety of setups For more information on this...

Page 23: ...digital inputs Figure 5 Terminal assignment for digital inputs Connection Short name Designation 5 DI1 Digital input 1 6 DI2 Digital input 2 7 DI3 Digital input 3 8 DI4 Digital input 4 9 Not assigned...

Page 24: ...nputs Table 7 Counter input pin assignments Figure 6 Counter input pin assignments Connection Short name Explanation 5 DI1 Counter input 1 configurable 6 DI2 Counter input 2 configurable 7 DI3 Counter...

Page 25: ...voltages Only SELV PELV voltages shall be connected to the device terminals Table 8 Terminal assignment for digital outputs Figure 7 Terminal assignment for digital outputs Connection Short name Desig...

Page 26: ...n Description 1 Not assigned 2 TXD 3 RXD 4 Not assigned 5 GND 6 Not assigned 7 Not assigned 8 Not assigned 9 Not assigned Table 10 PC interface cable assignment WAGO TO PASS PC D Sub 9 Pin Description...

Page 27: ...is activated Initialization takes approx 40 s after system start up if everything is OK SMS GPRS processing Antenna is not connected the modem is searching for a network Poor GSM network the modem is...

Page 28: ...4 sol Stripped length 9 mm 10 mm 3 6 2 Supply Table 13 Technical Data Supply Operating voltage 10 V 30 VDC Nominal voltage operation with mains power 24 VDC Nominal voltage operation using battery 12...

Page 29: ...Number of inputs 4 Input type Type 3 acc to IEC 61131 2 Input voltage 0 V 30 V DC Signal voltage 0 0 V 5 V DC Signal voltage 1 7 V 30 V DC Input current max at 30 V DC 2 9 mA 3 6 6 Counter Inputs Tab...

Page 30: ...per Article 3 2 RoHS Device complies with European RoHS directive FCC Verification per FCC 15b Approval Canada Approval Croatia Approval Mexico Approval Turkey 3 8 Standards and Guidelines 761 112 tel...

Page 31: ...ambient temperature of 20 C to 70 C In the event of higher or lower temperatures proper cooling or heating arrangements must be provided Please contact WAGO Kontakttechnik GmbH Co K G for assistance T...

Page 32: ...g the TO PASS telecontrol module from the DIN rail Figure 11 Removing the TO PASS telecontrol module from the DIN rail 1 Press the undersurface against the lower DIN rail edge until the TO PASS teleco...

Page 33: ...connection these must be connected in an up circuit wiring assembly for example using WAGO feed through terminals Terminate both solid and ferruled conductors without actuation by simply pushing them...

Page 34: ...il The shield connection of the TO PASS telecontrol module shield terminal 38 must be connected to the DIN rail The DIN rail must have a low impedance ground see section Connections Ground 5 2 1 Digit...

Page 35: ...PELV voltages Only SELV PELV voltages shall be connected to the device terminals Connect shielding Shielded cables are recommended for the counter inputs When using shielded cables the shield must be...

Page 36: ...761 112 Telecontrol Module Compact Web Manual Version 2 0 0 5 2 3 Digital Outputs Only connect SELV PELV voltages Only SELV PELV voltages shall be connected to the device terminals Figure 14 Connectio...

Page 37: ...using a double click 5 Select the CD drive in which you have placed the CD with the operating software 6 Start the WAGO TO PASS_SETUP 2 17 EXE program or a newer version in the main directory on the...

Page 38: ...O PASS telecontrol module it must first be configured with the telephone number 1 Every TO PASS telecontrol module requires an SIM card for proper operation You can obtain an SIM card from any mobile...

Page 39: ...IN button so that the TO PASS telecontrol module does not use the PIN code Also deactivate the PIN on the SIM card To do this insert the SIM card into a cell phone and under menu item Security select...

Page 40: ...og ISDN Select the type of connection for communicating with the TO PASS telecontrol module RS 232 Direct connection via RS 232 cable GSM Dial up using GSM modem on the PC Analog Dial up using analog...

Page 41: ...OM1 COMx Here select the serial interface where the communication cable is connected with a RS 232 connection Language English German French Select the langauge for the TO PASS operator interface here...

Page 42: ...have set the type of connection for communicating with the TO PASS telecontrol module you are then able to read out the parameters of the connected module Select the menu option Edit Read Parameters T...

Page 43: ...be configured from the project tree under it select the Identity option On the right side you will find the selection field for the function the display field for the name the input field for the tel...

Page 44: ...nd enter the PIN number in the field provided Roaming Roaming is always activated in TO PASS telecontrol modules To select a favorite carrier click the Allow button and enter the 5 digit carrier ID in...

Page 45: ...s are sent by the TO PASS telecontrol module as SMS however they can also be sent as an e mail fax or voice mail as defined in configuration The TO PASS telecontrol module can also transmit messages t...

Page 46: ...address e g for a T Mobile SIM card 8000 receiver provider net Transmission as fax Follow the instructions from the provider for transmissions as fax messages For T Mobile or Vodafone for example ent...

Page 47: ...r transmitting the data of the logger APN access In this field enter the APN access point Access Point Name for the SIM card provider e g T Mobile internet t mobile Vodafone web vodafone de The specif...

Page 48: ...nputs Digital inputs 1 4 can be configured as counter inputs starting from Firmware Version FW 2 33 The counters count up or down from the given starting and end value With upward counting exceeding o...

Page 49: ...the visualization system This function is available starting with Firmware Version FW 2 33 Starting value In this field enter the starting value for the counter This field is only active when the inp...

Page 50: ...plications with GPRS transmission Analog value Use these buttons to select up to four analog values which can also be transmitted with the message when the digital input has been set or when the count...

Page 51: ...th GPRS transmission Analog value Use these buttons to select up to four analog values which can also be transmitted with the deactivation message when the digital input has been reset or when the cou...

Page 52: ...owing applies in this case DI1 20 1 DI2 21 2 DI3 22 4 and DI4 23 8 Thus for example if DI1 and DI3 are set then the binary number is 5 If only DI4 is set then the binary number is 8 In the multiplex t...

Page 53: ...able Addresses Multiplex operation Click the button Use to enable disable multiplex operation for digital inputs DI1 DI4 If a status combination of digital inputs DI1 DI4 is fulfilled in multiplex ope...

Page 54: ...ultiplex Input entry The input fields for the alarm texts pertaining to the 16 statuses are provided on the right side Figure 21 Configuring multiplex operation alarm texts Table 24 Configuring multip...

Page 55: ...nects the DC voltage available at terminal 37 to the corresponding output Deactivation text In this field enter the deactivation text for the output When the TO PASS telecontrol module receives this t...

Page 56: ...lation packet size Please note the information given on calculation packet size in the Section Important Information Rounding of Blocks for GPRS Links 6 11 1 Alarm Messages for Digital Inputs If on or...

Page 57: ...elecontrol module waits for an acknowledgement after transmitting an alarm SMS Acknowledgement is in the form of an SMS containing the configured response text or a simple call by the recipient to the...

Page 58: ...ct the TO PASS telecontrol module from the project tree using the identifier Select the entry Repeat times under the option Special Functions The input fields for the Web interval the Web outputs and...

Page 59: ...function is available starting with Firmware Version FW 2 33 Switching input In this field select a digital input to be used for switching of the transmission interval between Web interval Off status...

Page 60: ...imes of day Time adjustment must be performed for limited SMS transmission to check the day of the week and the active time The first SMS is transmitted when the starting value for the active time on...

Page 61: ...nt Table 28 Setting the time adjustment Settings Time adjustment The TO PASS telecontrol module sends an SMS to itself and receives the current time from the provider transmitted by this SMS when the...

Page 62: ...have adapted all parameters for the TO PASS telecontrol module to your requirements you have to write the parameters to the connected module Select the menu option Edit Write Parameters The software...

Page 63: ...ol Module Compact Web Manual Version 2 0 0 6 13 1 Operation 6 14 Remote Query of Process Values The TO PASS telecontrol module offers two options for remote inquiry of the process values available Que...

Page 64: ...ays the alarms that are still possible per hour The alarm counter only transmitted when enabled Alarm counter parameter in the Identifier dialog 0 If at least one digital input is configured as a coun...

Page 65: ...Explanation 0 Digital input not configured as a counter e ZW Counter is active Counter value d ZW Counter is not active Counter value o ZW Counter overflow Counter vlaue r ZW Counter has been reset C...

Page 66: ...lay the process values with the TO PASS operator program select the menu item Visualization Process values The program establishes a link to the TO PASS telecontrol modules selected Please note the mo...

Page 67: ...lues of the inputs and outputs The process values displayed are valid if the on line display is green Figure 26 Visualization of the process values Process values pertaining to inputs are displayed in...

Page 68: ...process values click the Counter button possible only when inputs have been configured as counters The process values displayed are valid when the on line indicator is highlighted in green Figure 27...

Page 69: ...ol Module Compact Web Manual Version 2 0 0 7 1 2 Telecontrol TO PASS telecontrol modules offer the option of influencing a process remotely with the help of their analog and digital outputs There are...

Page 70: ...command with an SMS containing the identifier and the transmitted text Example Table 32 Example of parameters for Set DO Parameter Setting Activation text DOUT1 1 Deactivation text DOUT1 0 Turn off ti...

Page 71: ...ble 33 Control commands for counters Control command Function Cx x 1 4 Select counter 1 4 E Activate counter D Deactivate counter R Reset counter n e g 500 Set counter value Control commands must be c...

Page 72: ...lay the process values with the TO PASS operator program select the menu item Visualization Process values The program establishes a link to the TO PASS telecontrol modules selected Please note the mo...

Page 73: ...ess values displayed are valid if the on line display is green Figure 28 Visualization of the process values Process values pertaining to inputs are displayed in the upper portion of the window and th...

Page 74: ...ator is highlighted in green Figure 29 Counter process values The counter statuses are shown at the top of the window while the counter values the starting and end values and the limits are shown at t...

Page 75: ...receive an acknowledgement SMS containing the identifier the response text and the alarm text Acknowledgement by phone call is based on the card being used Some data cards do not allow voice links me...

Page 76: ...modules specifically to the respective ready state This takes place with simple changeover via SMS To do this just send an SMS with the text Standby1 to the TO PASS telecontrol modules The TO PASS te...

Page 77: ...splayed Figure 30 Test inputs and outputs The process values of the inputs are displayed in the upper area and the process values of the outputs are displayed in the lower area By pressing the buttons...

Page 78: ...nd values and the limits are shown at the bottom To start a counter click the button Activate To stop a counter click the button Deactivate To restore the counter to its starting value click the butto...

Page 79: ...direct serial link to the TO PASS telecontrol module To test the connection select the menu option Edit Test SMS GPRS The following window is displayed Figure 32 Testing the connection Select the addr...

Page 80: ...required The modem test may only be performed with a direct serial link to the TO PASS telecontrol module To test the mode select the menu item Modem Test The following window is displayed Figure 33...

Page 81: ...rovider for APN access user name and password see also Section Parameter setting Addresses Under Special Functions select Repetition Time and set the WEB Interval for the cyclic transmission to the We...

Page 82: ...he character 9 2 1 Example HTTP Request The HTTP request consists of both header and data string which are separated by an empty line CR LF Carriage Return Line Feed To improve readability line breaks...

Page 83: ...ensions In the data set descriptions the maximum number of characters is indicated in square brackets Starting from Firmware Version 02 33 08 you can select the script version to be applied to data tr...

Page 84: ...A1 Analog input 1 Value 6 Unit 5 Alarm 1 12 A2 Analog input 2 Value 6 Unit 5 Alarm 1 13 A3 Analog input 3 Value 6 Unit 5 Alarm 1 14 A4 Analog input 4 Value 6 Unit 5 Alarm 1 15 A5 Analog input 5 Value...

Page 85: ...To improve readability line breaks have been inserted ID TO PASS 12345 PA 0000 home 99 TI 11 05 05 14 34 21 D1 1 0 D2 0 0 D3 0 0 D4 0 0 D5 0 0 D6 0 0 D7 0 0 D8 0 0 A1 00 00 mA 0 A2 00 00 mA 0 A3 00 00...

Page 86: ...1 Alarm 1 11 D8 Digital input 8 Value 1 Alarm 1 12 A1 Analog input 1 Value 6 Unit 5 Alarm 1 13 A2 Analog input 2 Value 6 Unit 5 Alarm 1 14 A3 Analog input 3 Value 6 Unit 5 Alarm 1 15 A4 Analog input 4...

Page 87: ...viation is not enabled 1 Position deviation is enabled Flag 3 0 GPS receiver is turned off 1 GPS receiver is turned on Flag 4 0 No valid position available 1 Valid position available Flag 5 0 Static m...

Page 88: ...been inserted ID TO PASS Ext 12345 SV 01 01 PA 0000 home 99 TI 11 05 05 12 19 51 D1 0 0 D2 0 0 D3 0 0 D4 0 0 D5 0 0 D6 0 0 D7 0 0 D8 0 0 A1 00 00 mA 0 A2 00 00 mA 0 A3 00 00 mA 0 A4 00 00 mA 0 A5 00 0...

Page 89: ...DO 0000 AO 000 0 04 00 mA C1 0 0 0 C2 r 20F5800 0 C3 r 0 0 C4 0 0 0 SQ 21 US Hello MA 00 00 0 MV 0026 0000 002E 0064 0026 0000 0054 0064 HT 1 value always 1 the device time has not been set TI entry i...

Page 90: ...1 First value reached transgressed 2 Second value reached transgressed If both values are reached simultaneously only status 2 is transmitted SQ Signal quality or modem connection without formatting T...

Page 91: ...000 home 99 TI 11 05 05 12 19 51 D1 0 0 D2 0 0 D3 0 0 D4 0 0 D5 0 0 D6 0 0 D7 0 0 D8 0 0 A1 00 00 mA 0 A2 00 00 mA 0 A3 00 00 mA 0 A4 00 00 mA 0 A5 00 00 mA 0 A6 00 00 mA 0 A7 00 00 mA 0 A8 00 00 mA 0...

Page 92: ...econtrol Module Compact Web Manual Version 2 0 0 10 2 2 Logger Script Data transmission to the logger script is activated via cyclical transmission repetitions Web interval Data packet information con...

Page 93: ...ta Set Byte 0 1 2 3 4 5 6 Bit 76543210765432107654321076543210765432107654321076543210 Cont PNNNNNNNSJJJJJMMMMDDDDDhhhhhmmmmmmssssssDIN AIN1 Byte 7 8 9 10 11 12 13 Bit 76543210765432107654321076543210...

Page 94: ...ine breaks have been inserted ID TO PASS 12345 PA 0005 home 99 TI 11 05 05 14 36 11 LO 092D4AD100000000000000000000 562D4AD123000000000000000000 3F2D4AD12A000000000000000000 562D4AD1370000000000000000...

Page 95: ...7 LPD2 2 GPS message 81 see LPDx variable data format table 8 LIO3 3 I O message 74 see LIOx variable data format table 9 LPD3 3 GPS message 81 see LPDx variable data format table 10 LIO4 4 I O messag...

Page 96: ...put Value 3 10 7 analog input Value 3 11 8 analog input Value 3 12 Supply voltage Value 3 13 Digital output image Image 1 14 1 analog output Value 3 15 2 analog output Value 3 10 2 4 1 1 Data Format f...

Page 97: ...000 000 000 000 000 B89 0 000 000 LPD3 C0 11 05 05 06 34 25 276 C41 2600 N 216 1621 E 0C 4D34 3 26A F 21 11 7 0 LIO4 001C 56 11 05 05 08 34 36 00 000 000 000 000 000 000 000 000 B83 0 000 000 LPD4 C0...

Page 98: ...44 0x2C 2C Altitude in m 51 5 51 5 10 515 0x203 203 Position accuracy 2 2 Direction 309 35 309 x 60 35 18575 0x488F 488F Speed in km h 3 7 3 7 10 37 0x25 25 Speed in knots 2 0 2 0 10 20 0x14 14 Number...

Page 99: ...ue 2nd input hexadecimal Value 8 4 Counter status 3rd input Status 1 5 Counter value 3rd input hexadecimal Value 8 6 Counter status 4th input Status 1 7 Counter value 4th input hexadecimal Value 8 The...

Page 100: ...09 16 00 003 32E 7D5 7D9 7DA 7D8 7D6 7D5 AD0 0 000 32D LCD1 0 0 r 54600 r 0 0 0 LIO2 0001 11 00 01 01 00 09 52 00 CE3 32E 7D5 7D8 7DA 7D7 7D6 7D4 ACE 0 D04 32D LCD2 0 0 e 54600 d 0 0 0 LIO3 0002 78 0...

Page 101: ...l Version 2 0 0 10 2 4 3 Time Request Script FW 2 33 If time adjustment is to take place via the Internet a time request script is transmitted on system start in order to adjust the time when a reply...

Page 102: ...02 33 08 setpoint settings for digital and analog outputs and for changing the counters can be transmitted as replies Table 47 Setpoint settings Variable Contents Format AO1 1 analog output Normalized...

Page 103: ...rver Apache CR LF Content length 31 CR LF Keep alive timeout 15 max 100 CR LF Connection Keep Alive CR LF Content type text html CR LF CR LF Values stored 08 09 19 13 22 23 The header depends on both...

Page 104: ...ng example switching contact at counter input DI1 35 Figure 14 Connection example for a relay at DO1 output 36 Figure 15 General settings 40 Figure 16 Configuring the identity 43 Figure 17 Configuring...

Page 105: ...ts 49 Table 23 Configuring multiplex operation settings 53 Table 24 Configuring multiplex operation alarm texts 54 Table 25 Configuring the digital outputs 55 Table 26 Configuring the acknowledgement...

Page 106: ...106 List of Tables WAGO TO PASS 761 761 112 Telecontrol Module Compact Web Manual Version 2 0 0...

Page 107: ...WAGO TO PASS 761 107 761 112 Telecontrol Module Compact Web Manual Version 2 0 0...

Page 108: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 49 5 71 8 87 0 Fax 49 5 71 8 87 1 69 E Mail info wago com Internet http www wago com...

Reviews: