2.1.1.9 Datatransfer
With the control and status byte the controlling of the sending and receive
mode takes place. Requests are indicated by a bit change of state. An assigned
bit indicates execution by adopting the value of the request bit.
Initialization of the module:
Set IR bit in the control byte
Initialization of the module
Transmit/receive functions are blocked
Output/input buffers are erased
Serial interface module will load its configuration data
Transmitting data:
TR
TA: put characters into output bytes 0 to 2
Amount of characters is specified in OL0 to OL2
TR is inverted and read out
characters are put into output buffer if TR=TA
Receiving data:
RR
RA: data in input bytes 0 to 2 characters are available
Amount of characters is specified in IL0 to IL2
Characters in IL0 to IL2 are read out
RA is inverted and read out
All characters are read when RR=RA
The transmitting and receiving of data can be done simultaneously. The
initialization request has priority and will stop transmitting and receiving of
data immediately.
Attention
Resetting the initialization bit can be performed with the following message.
Message: input buffer full (Bit 3)
Input buffer is full. Data which is being currently received is now lost.