750-641 [DALI/DSI Master Module]
•
19
Process Data
WAGO-I/O-SYSTEM 750
I/O Modules
2.1.1.6.2.4 DALI Addressing Sheme
Every DALI device (electronic ballast) is able to react to a short address, 16
group addresses and broadcast. Each type of addresses is coded in an address
byte.
Address type
Address byte
Short or group address
YAAA AAAS
64 Short addresses
0AAA AAAS
16 Group addresses
100A AAAS
Collective address
111 111S
Y: Address type:
Y=‘0‘ Short address,
Y=‘1‘ Group address or collective address
A: Significant address bit
S:
Selection bit:
S=‘0‘, Direct lamp power value is following
S=‘1‘, Command is following in the next byte
2.1.1.6.2.5 Command Sets acc. to DIN IEC 60929 (dated: Draft July 2001)
DALI Commands (Request)
Output Data
D0
D1
D2
D3
D4
No.
Command
Code
DALI
Address
=0
=0
=0
Function
0
0000 0000
YAAA AAA1
0
0
0000 0000 Off
1
0000 0001
YAAA AAA1
0
0
0000 0000 Up
2
0000 0010
YAAA AAA1
0
0
0000 0000 Down
3
0000 0011
YAAA AAA1
0
0
0000 0000 Step up
4
0000 0100
YAAA AAA1
0
0
0000 0000 Step down
5
0000 0101
YAAA AAA1
0
0
0000 0000 Recall Max – Level
6
0000 0110
YAAA AAA1
0
0
0000 0000 Recall Min – Level
7
0000 0111
YAAA AAA1
0
0
0000 0000 Step down and off
8
0000 1000
YAAA AAA1
0
0
0000 0000 On and step up
9-15
0000 1XXX
YAAA AAA1
0
0
0000 0000 Reserved
16-31 0001 XXXX
YAAA AAA1
0
0
0000 0000 Go to scene 1 - 16
32 *) 0010 0000
YAAA AAA1
0
0
0000 0000 Reset
33 *) 0010 0001
YAAA AAA1
0
0
0000 0000 Store actual Level in the DTR **)
34–41
*)
0010 XXXX
YAAA AAA1
0
0
0000 0000 Reserved
42 *) 0010 1010
YAAA AAA1
0
0
0000 0000 Store the DTR **)
as Max – Level
43 *) 0010 1011
YAAA AAA1
0
0
0000 0000 Store the DTR **)
as Min – Level
44 *) 0010 1100
YAAA AAA1
0
0
0000 0000 Store the DTR **)
as System Failure – Level
45 *) 0010 1101
YAAA AAA1
0
0
0000 0000 Store the DTR **)
as Power On Level
46 *) 0010 1110
YAAA AAA1
0
0
0000 0000 Store the DTR **)
as Fade Time
47 *) 0010 1111
YAAA AAA1
0
0
0000 0000 Store the DTR **)
as Fade Rate
48–63
*)
0011 XXXX
YAAA AAA1
0
0
0000 0000 Reserved
64-79
*)
0100 XXXX
YAAA AAA1
0
0
0000 0000 Store the DTR **)
as Scene1 -16
80-95
*)
0101 XXXX
YAAA AAA1
0
0
0000 0000 Remove from Scene 1 - 16
96-
111 *)
0110 XXXX
YAAA AAA1
0
0
0000 0000 Add to Group 1 - 16
112 *) 0111 XXXX
YAAA AAA1
0
0
0000 0000 Remove from Group 1 -16
128 *) 1000 0000
YAAA AAA1
0
0
0000 0000 Store the DTR **)
as Short Address
129–
143
1000 XXXX
YAAA AAA1
0
0
0000 0000 Reserved
144
1001 0000
YAAA AAA1
0
0
0000 0000 Query Status
145
1001 0001
YAAA AAA1
0
0
0000 0000 Query Ballast
146
1001 0010
YAAA AAA1
0
0
0000 0000 Query Lamp Failure
147
1001 0011
YAAA AAA1
0
0
0000 0000 Query Lamp Power On
148
1001 0100
YAAA AAA1
0
0
0000 0000 Query Limit Error