![WAGO 750-612/040-000 Manual Download Page 47](http://html1.mh-extra.com/html/wago/750-612-040-000/750-612-040-000_manual_868481047.webp)
WAGO I/O SYSTEM 750 XTR
Use in Hazardous Environments 47
750-624/040-00x Field Supply Filter 24 VDC HI XTR
Manual
Version 1.4.0
Figure 21: Text Detail – Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Table 27: Description of Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Marking
Description
Dust
Ex
Explosion protection mark
nA
Type of protection
[ia IIIC]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)
X
Symbol used to denote specific conditions of use
Gases
Ex
Explosion protection mark
nA
Type of protection
[ia Ga]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 0
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)
X
Symbol used to denote specific conditions of use