78 Commissioning
WAGO-I/O-SYSTEM 750
750-564 4AO U/I
Manual
Version 1.0.0
7.3.2.4 PROFIBUS DP Fieldbus Couplers
750-333(/0xx-000), 750-833(/0xx-000)
The PROFIBUS fieldbus couplers also allow diagnostics to be enabled on a
channel basis and substitute values to be set if the setting “Substitute values are
switched” was selected for the “Response to PROFIBUS DP failure” on the
station representative.
7.3.2.5 PROFINET IO Fieldbus Couplers
750-375(/025-000), 750-377(/025-000)
The PROFINET fieldbus couplers allow the (sub) module and channel-specific
activation of the events to be used for station diagnostics, their actual activation
and other channel-specific settings of the I / O module.
Table 59: General Module/Channel Parameters
3)
– PROFINET IO Couplers
GSD File
WAGO-I/O-
CHECK
Name
Value
Selection field Value
Substitute value
behavior [Channel x
(x = 0…3)]
According to the device settings
*)
n/a
n/a
Keep last valid value
Set substitute value
Substitute value
[Channel x
(x = 0…3)]
0
*)
… 65535
1)
−
32768 … 0
*)
… 32767
2)
n/a
n/a
*)
Factory setting
1)
16-bit resolution
2)
15-bit resolution
3)
You can find further explanations in the manuals for the PROFINET fieldbus couplers/
controllers
Table 60: Specific Module/Channel Parameters – PROFINET IO Couplers
GSD File
WAGO-I/O-
CHECK
Name
Value
Selection field
Value
Diagnostics:
Power supply fault
[I/O module]
0 (false)
Diagnosis:
Power supply fault
[Common]
Off
1 (true)
*)
On
*)
Diagnostics:
AO− wiring error
[I/O module]
0 (false)
Diagnosis:
wiring error
AO−
[Common]
Off
1 (true)
*)
On
*)
Channel diagnostics
[Channel x (x = 0…3)]
0 (false)
*)
Channel diagnosis
[Channel x (x = 1…4)]
Off
1 (true)
On
*)
Table 58: General Module/Channel Parameters
3)
– PROFIBUS DP Fieldbus Couplers
GSD File
WAGO-I/O-
CHECK
Name
Value
Selection field
Value
Diagnostics
[Channel x (x =
0…3)]
disabled
*)
Channel diagnosis
[Channel x
(x = 1…4)]
Off
*)
enabled
On
Substitute value
[Channel x (x =
0…3)]
0
*)
… 65535
1)
−
32768 … 0
*)
… 32767
2)
n/a
n/a
*)
Factory setting
1)
16-bit resolution
2)
15-bit resolution
3)
You can find further explanations in the manuals for the PROFIBUS fieldbus couplers/
controllers.