WAGO-I/O-SYSTEM 750
Device Description
23
750-530 8DO 24V DC 0.5A
Manual
Version 1.2.0
Pos: 45.1 /All e Seri en ( Allgemei ne Module)/Ü berschriften für alle Serien/Gerätebeschreibung/Anschlusstechni k - Ü berschrift 3 @ 17\mod_1380123271324_21.docx @ 132788 @ 3 @ 1
3.5.5
Connection Type
Pos: 45.2 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung/T echnische Daten/T echnische D aten Verdr ahtungsebene CC - 0,08 bis 2,5mm2 @ 17\mod_1380121238809_21.docx @ 132780 @ @ 1
Table 12: Technical Data – Field Wiring
Wire connection
CAGE CLAMP
®
Cross section
0.08 mm² … 2.5 mm², AWG 28 … 14
Stripped lengths
8 mm … 9 mm / 0.33 in
Pos: 45.3 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung/T echnische Daten/Anschlusstechni k/T echnische D aten Leistungskontakte (Messer/Feder) @ 17\mod_1380123464149_21.docx @ 132791 @ @ 1
Table 13: Technical Data – Power Jumper Contacts
Power jumper contacts
Blade/spring contact, self-cleaning
Voltage drop at I
max.
< 1 V/64 modules
Pos: 45.4 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebeschrei bung/T echnische Daten/Anschlusstechni k/T echnische D aten Datenkontakte @ 17\mod_1380123495844_21.docx @ 132794 @ @ 1
Table 14: Technical Data – Data Contacts
Data contacts
Slide contact, hard gold plated, self-
cleaning
Pos: 46 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebeschrei bung/T echnische Daten/Kli matische U mg ebungsbedi ngungen/Technische Daten Klimat. U mgebungsbed. mi t erw. T emp. -20...+60°C /-40...+85°C für /025 @ 5\mod_1247658089120_21.docx @ 37606 @ 3 @ 1
3.5.6
Climatic Environmental Conditions
Table 15: Technical Data – Climatic Environmental Conditions
Operating temperature range
0 °C … 55 °C
Operating temperature range for
components with extended
temperature range (750-xxx/025-xxx)
−
20 °C … +60 °C
Storage temperature range
−
25 °C … +85 °C
Storage temperature range for
components with extended
temperature range (750-xxx/025-xxx)
−
40 °C … +85 °C
Relative humidity
Max. 5 % … 95 % without condensation
Resistance to harmful substances
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
Maximum pollutant concentration at
relative humidity < 75 %
SO
2
≤
25 ppm
H
2
S
≤
10 ppm
Special conditions
Ensure that additional measures for
components are taken, which are used in
an environment involving:
– dust, caustic vapors or gases
– ionizing radiation
Pos: 47 /D okumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1