14
Device Description
WAGO-I/O-SYSTEM 750
750-530 8DO 24V DC 0.5A
Manual
Version 1.2.0
Do not exceed maximum current via power jumper contacts!
The maximum current to flow through the power jumper contacts is 10 A.
Greater currents can damage the contacts.
When configuring your system, ensure that this current is not exceeded. If
exceeded, insert an additional supply module.
Pos: 20.13 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Ei nleitung/Versorgung/Gal vanische Trennung F eld/System @ 3\mod_1233756478750_21.docx @ 27102 @ @ 1
The field voltage and the system voltage are electrically isolated from each other.
Pos: 20.14 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Ei nleitung/Versorgung/Anordnung unter Ber ücksichtigung der Leistungskontakte beliebig @ 3\mod_1233756233468_21.docx @ 27099 @ @ 1
With consideration of the power jumper contacts, the individual modules can be
arranged in any combination when configuring the fieldbus node. An arrangement
in groups within the group of potentials is not necessary.
Pos: 20.15 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Ei nleitung/Einsatzbereich/Einsatzbereich 750- xxxx alle Koppler/C ontroll er ohne Ei nschränkung @ 3\mod_1232541691906_21.docx @ 26522 @ @ 1
The I/O module 750-530 can be used with all fieldbus couplers/controllers of the
WAGO-I/O-SYSTEM 750.