WAGO-I/O-SYSTEM 750 XTR
Appendix 293
750-495/040-00x 3-Phase Power Measurement Module 690 V
Manual
Version 1.2.0
Table 81: Register 46
Register 46 – Storage Interval, Energy Consumption
Function
Data Type Access
Factory Setting
Storing interval, energy consumption,
Resolution: 1 second
UINT
R/W
0x003C (60s)
0 … 59:
-not permitted-
60 … 255: Time in seconds up to automatic storage of energy values.
≥ 256:
-not permitted-
Table 82: Register 47
Register 47 – Error Register for the Parameter Channel
Function
Data Type
Access
Factory Setting
Error register for the parameter channel
UINT
R
0x0000
0:
Calibration procedure, no error
1:
Calibration procedure, division by zero
2:
Calibration procedure “Gain” > 2
3:
Calibration procedure, command sequence not followed
4:
Calibration procedure, calibration step not implemented
5:
Calibration procedure, the “period” register in the MCU microcontroller has never
been read before
≥6
:
-not permitted-
Table 83: Register 48
Register 48 – Container 1
Function
Data Type Access
Factory Setting
Container 1,
for energy meter and calibration preset
UINT
R/W
0x0000
Table 84: Register 49
Register 49 – Container 2
Function
Data Type Access
Factory Setting
Container 2,
for energy meter and calibration preset
UINT
R/W
0x0000
Table 85: Register 50
Register 50 – Container 3
Function
Data Type Access
Factory Setting
Container 3,
for energy meter and calibration preset
UINT
R/W
0x0000
Table 86: Register 51
Register 51 – Container 4
Function
Data Type Access
Factory Setting
Container 4,
for energy meter and calibration preset
UINT
R/W
0x0000