WAGO-I/O-SYSTEM 750
Diagnostics
99
750-494 3-Phase Power Measurement Module
Manual
Version 1.2.0
Pos: 101 /Alle Serien (Allgemei ne M odul e)/Ü berschriften/Ebene 1/Di agnose - Überschrift 1 @ 4\mod_1240831069471_21.docx @ 31372 @ 1 @ 1
9
Diagnostics
Pos: 102 /Serie 750 (WAGO-I/O-SYST EM)/Diagnose/Busklemmen/Diagnose 750- 0494, - 0495 @ 13\mod_1348662372924_21.docx @ 103550 @ @ 1
LED A indicates the operating status, LEDs B … H indicate possible errors.
The meaning of these indications is as follows:
Table 22: Diagnostics
LED
State
Message
A
Off
No operational readiness or
the internal data bus communication is interrupted.
Note: If the watchdog was disabled, the LED is
always green. See section “Commissioning” >
“Configuration with WAGO-I/O-
CHECK
”.
Green
Operational readiness and correct internal data bus
communication
B
Off
No error
Red
General error message for L1:
Under-/overvoltage or overcurrent
C
Off
No error
Red
General error message: Clipping of a current
measuring path IL1, IL2 or IL3
D
Off
No error
Red
High measuring error, caused by undershooting the
min. voltage at L1, L2 or L3
E
Off
No error
Red
General error message for L2:
Under-/overvoltage or overcurrent
F
Off
No error
Red
General error message for L3:
Under-/overvoltage or overcurrent
G
Off
No error
Red
General error message: Clipping of a voltage
measuring path L1, L2 or L3
H
Off
No error
Yellow Error of the phase sequence L1-L2-L3