750-481/003-000 [2 AI RTD EEx i]
•
9
Display
Elements
WAGO-I/O-SYSTEM 750
I/O Modules
Note
If the employment of further DC 24 V EEx i Supply modules is necessary for
reasons of extent of utilization, four Separation modules (750-616) must be
used to guarantee the distance between the intrinsically safe segments.
Warning
The maximum current of the internal power jumper contacts is 10 A. When
configuring the system it is important not to exceed the maximum/sum
current. However, if such a case should occur, another supply module must be
added.
The analog input module 750-481/003-000 can be used with all
couplers/controllers of the WAGO-I/O-SYSTEM 750 (except for the economy
types 750-320, -323, -324 and -327).
Further Information
General information on explosion prevention is described in the manual in
section “Use in Hazardous Environments“!
2.1.1.3 Display
Elements
LED
Channel Meaning State Function
off
No operational readiness or the
internal data bus communication
is interrupted
green
Function
AI 1
on
Operational readiness and
trouble-free internal data bus
communication
off Normal
operation
red
1
Error
AI 1
on
Overrange/underflow of the
admissible measuring range,
broken wire, short circuit
off
No operational readiness or the
internal data bus communication
is interrupted
green
Function
AI 2
on
Operational readiness and
trouble-free internal data bus
communication
off Normal
operation
13
14
15
16
Function AI 1
Error AI 1
Function AI 2
Error AI 2
Fig. 2.1.1-2: Display
Elements
g048102d
red
2
Error
AI 2
on
Overrange/underflow of the
admissible measuring range,
broken wire, short circuit