WAGO-I/O-SYSTEM 750 XTR
Process Image
37
750-469/040-000 2AI Thermocouple configurable /XTR
Manual
Version 1.3.0
Table 24: Process Image Type T, With Wire Break Diagnostics
Temperature
°C
Numeric value
1)
Status
byte
hex.
LED
error
AI 1, 2
Binary
Hex.
Dec.
< approx.
−100.1
'1111.1100.0001.0111'
0xFC17
−1001
0x41
ON
−100.0
'1111.1100.0001.1000'
0xFC18
−1000
0x00
OFF
−50.0
'1111.1110.0000.1100'
0xFE0C
−500
0x00
OFF
0.0
'0000.0000.0000.0000'
0x0000
0
0x00
OFF
50.0
'0000.0001.1111.0100'
0x01F4
500
0x00
OFF
100.0
'0000.0011.1110.1000'
0x03E8
1000
0x00
OFF
150.0
'0000.0101.1101.1100'
0x05DC
1500
0x00
OFF
200.0
'0000.0111.1101.0000'
0x07D0
2000
0x00
OFF
250.0
'0000.1001.1100.0100'
0x09C4
2500
0x00
OFF
300.0
'0000.1011.1011.1000'
0x0BB8
3000
0x00
OFF
350.0
'0000.1101.1010.1100'
0x0DAC
3500
0x00
OFF
400.0
'0000.1111.1010.0000'
0x0FA0
4000
0x42
OFF
> 400.0
'0000.1111.1010.0000'
> 0x0FA0
> 4000
0x42
ON
Wire break
'0111.1111.1111.1111'
0x7FFF
32767
0x42
ON
1)
Temperature values below 0 °C are represented in two's complement binary.
Table 25: Process Image Type J, With Wire Break Diagnostics
Temperature
°C
Numeric value
1)
Status
byte
hex.
LED
error
AI 1, 2
Binary
Hex.
Dec.
<
−100
'1111.1100.0001.1000'
0xFC18
−1000
0x41
ON
−100.0
'1111.1100.0001.1000'
0xFC18
−1000
0x00
OFF
0.0
'0000.0000.0000.0000'
0x0000
0
0x00
OFF
100.0
'0000.0011.1110.1000'
0x03E8
1000
0x00
OFF
200.0
'0000.0111.1101.0000'
0x07D0
2000
0x00
OFF
300.0
'0000.1011.1011.1000'
0x0BB8
3000
0x00
OFF
400.0
'0000.1111.1010.0000'
0x0FA0
4000
0x00
OFF
500.0
'0001.0011.1000.1000'
0x1388
5000
0x00
OFF
1000.0
'0010.0111.0001.0000'
0x2710
10000
0x00
OFF
1200.0
'0010.1110.1110.0000'
0x2EE0
12000
0x00
OFF
> 1200.0
'0010.1110.1110.0000'
> 0x2EE0
> 12000
0x42
ON
Wire break
'0111.1111.1111.1111'
0x7FFF
32767
0x42
ON
1)
Temperature values below 0 °C are represented in two's complement binary.