750-468 [4 AI DC 0-10 V, Single-Ended]
•
13
Process Image
WAGO-I/O-SYSTEM 750
I/O Modules
2.1.1.7.2 Special Data Format
To digitalize the measurement value, the variation 750-468/000-200 uses a
format adapted for the S5 control systems using FB 250.
For this variation, the input voltage ranging from 0 V to 10 V is scaled on the
numerical values ranging from 0x1000 to 0x5001.
Process values of module 750-468/000-200
Numerical value
Input voltage
binary
Status-
byte
0 V - 10 V
value
*
)
X F Ü
hex.
dec.
hex.
<0.00 '0001.0000.0000.0 000'
0x1000
4096
0x00
0.00 '0001.0000.0000.0 000'
0x1000
4096
0x00
1.25 '0001.1000.0000.0 000'
0x1800
6144
0x00
2.50 '0010.0000.0000.0 000'
0x2000
8192
0x00
3.75 '0010.1000.0000.0 000'
0x2800
10240
0x00
5.00 '0011.0000.0000.0 000'
0x3000
12288
0x00
6.25 '0011.1000.0000.0 000'
0x3800
14336
0x00
7.50 '0100.0000.0000.0 000'
0x4000
16384
0x00
8.75 '0100.1000.0000.0 000'
0x4800
18432
0x00
10.00 '0101.0000.0000.0 000'
0x5000
20480
0x00
>10.00 '0101.0000.0000.0 001'
0x5001
20481
0x42
*
)
status bits: X = not used, F = short-circuit, Ü = oversize