34
Process Image
WAGO-I/O-SYSTEM 750 XTR
750-453/040-000 4AI 0-20mA S.E. /XTR
Manual
Version 1.3.0
The following table shows examples:
Table 21: Process Image of the I/O Module, Examples of Process Values
Input
Current
0 mA
…
20 mA
Numeric Value
Status
Byte
Hex.
LED
Error
AI 1
…4
Binary
Measured Value
Binary
Diagn.
1)
Hex.
Dez.
0.0
'0000.0000.0000.0
000'
0x0000
0
0x00
OFF
2.5
'0001.0000.0000.0
000'
0x1000
4.096
0x00
OFF
5.0
'0010.0000.0000.0
000'
0x2000
8.192
0x00
OFF
7.5
'0011.0000.0000.0
000'
0x3000 12.288
0x00
OFF
10.0
'0100.0000.0000.0
000'
0x4000 16.384
0x00
OFF
12.5
'0100.1111.1111.1
000'
0x4FF8 20.472
0x00
OFF
15.0
'0101.1111.1111.1
000'
0x5FF8 24.568
0x00
OFF
17.5
'0110.1111.1111.1
000'
0x6FF8 28.664
0x00
OFF
20.0
'0111.1111.1111.1
000'
0x7FF8 32.760
0x00
OFF
18.0
'0111.0011.0011.0
000'
0x7330 29.488
0x00
OFF
20.0
'0111.1111.1111.1
000'
0x7FF8 32.760
0x00
OFF
> 20.0
'0111.1111.1111.1
011'
0x7FFB 32.763
0x42
ON
1)
Bit B2: not defined
Bit B1 and bit B0: Indicates if the measuring range is overrange