background image

 

 

750-433 [4 DI DC 24 V 0.2 ms / 2- conductor]    •  7 

 

 

View  

WAGO-I/O-SYSTEM 750 
I/O Modules 

2 I/O Modules 

2.1  Digital Input Modules 

2.1.1  750-433 [4 DI DC 24 V 0.2 ms / 2- conductor] 

4- Channel Digital Input Module DC 24 V 0.2 ms, 
2- conductor connection; high-side switching 

2.1.1.1 View 

13 14

+ +

15 16

13 14

C

D

B

A

+ +

DI 2

Power jumper contacts

Data contacts

DI 4

DI 2

Status

24V

24V

DI 4

DI 3

DI 1

Status

DI 1

DI 3

750-433

 

Fig. 2.1.1-1: 4- Channel Digital Input Module 750-433 

g043300e

 

2.1.1.2 Description 

The digital input module 750-433 receives control signals from digital field 
devices (sensors, etc.). 

The module has four input channels. Four 2-conductor sensors may be directly 
connected to the module. 

 

The sensors can be connected using connection 24 V and DI 1 or DI 2, DI 3, 
DI 4.  
The connection of 3-conductor sensors to this module requires a field side 
connection module (750-604 or 750-614) for 0 V supply. 

Each input module has an RC noise rejection filter with a time constant of 
0.2 ms. 

The status of the input channels is indicated via status LEDs.  

An optocoupler is used for electrical isolation between the bus and the field 
side. 

Summary of Contents for 750-433

Page 1: ...Fieldbus Independent I O Modules 4 DI DC 24 V 0 2 ms 2 conductor 750 433 Manual Version 1 0 2 ...

Page 2: ...0 571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the correctness and com pleteness of this documentation However as errors can never be fully ex cluded we would appreciate any information or ideas at any time E Mail documentation wago com We wish to point out that the software and hardware terms as well as the trademarks of companie...

Page 3: ...alification 4 1 1 3 Intended Use 4 1 2 Symbols 5 1 3 Number Notation 5 1 4 Safety Notes 6 1 5 Scope 6 2 I O Modules 7 2 1 Digital Input Modules 7 2 1 1 750 433 4 DI DC 24 V 0 2 ms 2 conductor 7 2 1 1 1 View 7 2 1 1 2 Description 7 2 1 1 3 Display Elements 8 2 1 1 4 Schematic Diagram 9 2 1 1 5 Technical Data 10 2 1 1 6 Process Image 11 ...

Page 4: ...nufacturers are always named without referring to patent rights The existence of such rights can therefore not be ruled out 1 1 2 Personnel Qualification The use of the product detailed in this manual is exclusively geared to specialists having qualifications in PLC programming electrical specialists or persons instructed by electrical specialists who are also familiar with the valid standards WAG...

Page 5: ...ration ESD Electrostatic Discharge Warning of damage to the components by electrostatic discharge Observe the precautionary measure for handling components at risk Note Routines or advice for efficient use of the device and software optimization More information References on additional literature manuals data sheets and INTERNET pages 1 3 Number Notation Number Code Example Note Decimal 100 norma...

Page 6: ...ormation is to be regarded Do not use any contact spray The spray may impair the functioning of the contact area The WAGO I O SYSTEM 750 and its components are an open system It must only be assembled in housings cabinets or in electrical operation rooms Access must only be given via a key or tool to authorized qualified personnel The relevant valid and applicable standards and guidelines concerni...

Page 7: ...3300e 2 1 1 2 Description The digital input module 750 433 receives control signals from digital field devices sensors etc The module has four input channels Four 2 conductor sensors may be directly connected to the module The sensors can be connected using connection 24 V and DI 1 or DI 2 DI 3 DI 4 The connection of 3 conductor sensors to this module requires a field side connection module 750 60...

Page 8: ...acts is 10 A When configuring the system it is important not to exceed the maximum sum current However if such a case should occur another supply module must be added The digital input module 750 433 can be used with all couplers controllers of the WAGO I O SYSTEM 750 2 1 1 3 Display Elements LED Channel Designation State Function off Input DI 1 Signal voltage 0 A green 1 Status DI 1 on Input DI 1...

Page 9: ... conductor 9 Schematic Diagram WAGO I O SYSTEM 750 I O Modules 2 1 1 4 Schematic Diagram DI 0V 10nF DI 10 nF 24V DI 1 DI 2 24V 0V DI 3 DI 4 0V 24V 2 6 1 3 4 5 7 8 750 433 Fig 2 1 1 3 4 Channel Digital Input Module 750 433 g043301e ...

Page 10: ...DIN rail Weight ca 50 g Standards and Regulations cf Chapter 2 2 of the Coupler Controller Manual EMC Immunity to interference CE acc to EN 61000 6 2 01 EMC Emission of interference CE acc to EN 50081 1 93 EMC Immunity to interference Ship building acc to Germanischer Lloyd 01 EMC Emission of interference Ship building acc to Germanischer Lloyd 01 Approvals cf Chapter 2 2 of the Coupler Controller...

Page 11: ...erview Approvals WAGO I O SYSTEM 750 which you can find on the CD ROM ELECTRONICC Tools and Docs Item No 0888 0412 or in the internet under www wago com Documentation WAGO I O SYSTEM 750 System Description 2 1 1 6 Process Image Input bit B3 B2 B1 B0 Meaning Signal status DI 4 Channel 4 Signal status DI 3 Channel 3 Signal status DI 2 Channel 2 Signal status DI 1 Channel 1 ...

Page 12: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastraße 27 D 32423 Minden Phone 05 71 8 87 0 Fax 05 71 8 87 1 69 E Mail info wago com Internet http www wago com ...

Reviews: