WAGO-I/O-SYSTEM 750 XTR
Device Description 23
750-404/040-003 Counter Adjust XTR
Manual
Version 1.1.0
3.6
Display Elements
Figure 5: Display Elements
Table 7: Legend for Figure “Display Elements”
Designation LED
State
Function
„U/D“ status
A
Off
Signal voltage (0) at input “U/D”:
•
Frequency Counter:
Measurement enabled
•
Up Counter:
Counting disabled
•
Up/Down Counter:
Count downward
•
2 Up Counter:
No count pulses
Green
Signal voltage (1) at input “U/D”:
•
Frequency Counter:
Measurement disabled
•
Up Counter:
Counting enabled
•
Up/Down Counter::
Count upward
•
2 Up Counter:
Second count pulse
Status DO 1
C
Off
Digital output DO 1 is reset.
Green
Digital output DO 1 is set.
CLOCK status E
Off
Signal voltage (0) at input “CLOCK”
Green
Signal voltage (1) at input “CLOCK”
*)
Status DO 2
G
Off
Digital output DO 2 is reset.
Green
Digital output DO 2 is set.
*)
Operating mode “Two up counters”: First count pulse