14.2 Parameters of the I/O Modules
The following subsections list the individual attribute values and descriptions for
parameterization of the various I/O modules. The default attribute values are
highlighted in “
bold
”.
14.2.1 Digital Input Modules (DI, DI DIA)
All digital input modules receive a parameter data set from the IO controller in the
form of a record write request to the data set number or index 0x4000 or 16384.
The following settings are possible for digital input modules with diagnostics.
Table 107: Parameterization – Overview of Attributes for Digital Input Modules with Diagnostics
(DI, DIA)
Attributes for the Digital Input Modules with Diagnostics (DI, DIA)
-
Diagnose
Table 108: Parameterization DI, DIA – “Diagnostics” Attribute
Attribute name
Attribute value
Description
Diagnostics
An external error on the respective signal channel:
lock (false)
•
does not lead to transmission of a diagnostic
alarm nor entry in the diagnostics database of
the station proxy.
release (true)
•
leads to transmission of a diagnostic alarm and
its entry in the diagnostics database of the
station proxy.