Table 46: General Channel Parameters
Parameter
Setting
Description
Diagnostics
channel x
For external faults, channel diagnostics and the
respective alarms are
lock
*)
•
not transmitted to the IO controller.
release
•
transmitted to the IO controller.
Process data format
channel x
Word or double-word-orientated process data of
the signal channel are transmitted to the IO
controller in:
according to the
device settings
*)
Format set for the station proxy..
INTEL (LSB-MSB) „Little Endian“ format
MOTOROLA
(MSB-LSB)
„Big Endian“ format“
Substitute output data
channel x
I/O module-specific
0x0000
*)
… 0xFFFF
When configuring the substitute value behavior of
the I/O module, these values are output to the
complex signal channel with invalid output data of
the IO controller.
Substitute output status
channel x
0
*)
… 1
When configuring the substitute value behavior of
the I/O module, these values are output to the
binary signal channel with invalid output status of
the IO controller.
*)
Default setting
8.6.6
Specific Channel Parameters
Some I/O modules have specific channel parameters in addition to the general
channel parameters. These I/O modules currently include:
750-450, 750-451, 75x-463, 75x-464, 75x-464/020-000,
75x-562, 75x-563,
75x-644, 75x-655, 75x-670, 75x-671, 750-672, 75x-673