192
•
Process Data Architecture for EtherNet/IP
Digital Output Modules
WAGO-I/O-SYSTEM
750
ETHERNET TCP/IP
Output Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Acknowledge
ment bit
Q 2
Channel 2
Acknowledg
ement bit
Q 1
Channel 1
0 0
And the input modules seize 4 Instances in Class (0x66).
4 Channel Digital Input Modules
750-402, -403, -408, -409, -414, -415, -422, -423, -428, -432, -433,
753-402, -403, -408, -409, -415, -422, -423, -428, -432, -433, -440
Input Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Data bit
DI 4
Channel
4
Data bit
DI 3
Channel
3
Data bit
DI 2
Channel
2
Data bit
DI 1
Channel
1
The input modules seize 4 Instances in Class (0x65).
8 Channel Digital Input Modules
750-430, -431, -436, -437, 753-430, -431, -434
Input Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Data bit
DI 8
Channel
8
Data bit
DI 7
Channel
7
Data bit
DI 6
Channel
6
Data bit
DI 5
Channel
5
Data bit
DI 4
Channel
4
Data bit
DI 3
Channel
3
Data bit
DI 2
Channel
2
Data bit
DI 1
Channel
1
The input modules seize 8 Instances in Class (0x65).
5.3.2 Digital Output Modules
Digital output modules use one bit of data per channel to control the output of
the corresponding channel. These bits are mapped into the Output Process
Image.
When analog output modules are also present in the node, the digital image
data is always appended after the analog data in the Output Process Image,
grouped into bytes.
Each output channel seizes one Instance in the Discrete Output Point Object
(Class 0x66).