WAGO I/O SYSTEM 750 XTR
Commissioning
93
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
8.4.1.3
Physical station design with activate
d parameter “Startup if expected
and actual configuration differ” 2
Figure 43:
Physical station design with activated parameter “Startup if expected and actual
configuration differ” 2 (sample)
If the parameter “Startup for preset configuration unlike actual configuration” is
activated for the fieldbus coupler in the role as a station proxy, the parameter
module slot “I/O module is physical” for the I/O modules receives the settings
“plugged in” or “optional not plugged”. If I/O modules should have been
configured as “optional not plugged” at the right end of the node and represented
by an extra module, the physical arrangement of the extra modules ‒ in this case
on slot 17 ‒ is optional.
The numbers in gray above the node represent the physical DP I/O module slot.
The configured slots are in light blue.
More information about the PI-configuration
An exact description of the PI-configuration for the fieldbus coupler and I/O
modules can be found in the
“PI-Configuration” chapter in the appendix.