206 Appendix
WAGO I/O SYSTEM 750 XTR
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
The table shows the parameterization properties of the 4 and 2-channel analog
input modules with asynchronous diagnostic properties and individual
parameters.
Table 159: Parameters of the 4(2)-channel analog input modules (AI_PAR)
4AI_PAR (2AI_PAR)
Representatives of the 4AI_PAR:
75x-463, 75x-464, 75x-464/020-000,
Representatives of the 2AI_PAR:
75x-464
Parameterization data length in bytes
Standard parameterization
Structured parameterization
6
10
Parameter
Settings
Description
Scope
Terminal is physically
The I/O module process data is
Module
(optionally) not plugged
•
(optionally) set to zero by the fieldbus
coupler.
plugged
*)
•
supplied by the I/O module.
Diagnosis
The diagnostic information of the corresponding
channel is
Channel
disabled
*)
•
not transmitted to the PROFIBUS DP
master.
enabled
•
transmitted to the PROFIBUS DP master.
Sensor type
2)
The sensor is of type
Channel
Pt1000 (IEC 751)
*)
•
Thermoresistor Pt1000
Ni1000 (DIN 43760)
•
Thermoresistor Ni1000
Ni1000 (TK 5000)
•
Thermoresistor Ni1000
KTY 81 110
•
Thermoresistor Si110
KTY 81 210
•
Thermoresistor Si210
Sensor type
3)
The sensor is of type
Channel
Pt100 (IEC 60751)
*)
•
Thermoresistor Pt100
Ni100 (DIN 43760)
•
Thermoresistor Ni100
Pt1000 (IEC 60751)
•
Thermoresistor Pt1000
Pt500 (IEC 60751)
•
Thermoresistor Pt500
Pt200 (IEC 60751)
•
Thermoresistor Pt200
Ni1000 (TK 6180, DIN 43760)
•
Thermoresistor Ni1000
Ni120 (Minco)
•
Thermoresistor Ni120
Ni1000 (TK 5000, DIN 43760)
•
Thermoresistor Ni1000
Potentiometer
1)
•
Potentiometer
Resistor 10R-5k (linear)
1)
•
Resistor 10R-5k (linear)
Resistor 10R-1k2 (linear)
1)
•
Resistor 0R-1k2 (linear)
Connection type
The sensor is connected by
Channel
2-wire connection
1)
•
2 conductors.
3-wire connection
•
3 conductors.
*)
Default settings
1)
Only in operating mode 2AI
2)
Applies to 75x-463