WAGO I/O SYSTEM 750 XTR
Diagnostics 113
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
9.3.5.1
Internal status messages and arguments
Table 61: Internal status messages and arguments
Device status
Description
Message
Argument
0x00
0x00
No fault
0x01
0x00
EEPROM checksum error / checksum error in parameter range of
FLASH memory
0x01
0x01
Overflow of inline code buffer
0x01
0x02
Unknown data type
0x01
0x03
Module type for flash program memory could not be determined / is
incorrect
0x01
0x04
Fault when writing into the FLASH memory
0x01
0x05
Fault when deleting the FLASH memory
0x01
0x06
Changed I/O modules configuration determined after AUTORESET
0x01
0x07
Fault when writing into the serial EEPROM.
0x01
0x08
Invalid firmware
0x02
0x00
Incorrect table entry
0x07
N
Module at position n (n = 1...63) is not supported
9.3.5.2
Local bus messages and arguments
Table 62: Local bus messages and arguments
Device status
Description
Message
Argument
0x43
0xFF
At least one module cannot interpret a local bus command
0x44
0x00
A data fault or a local bus interruption exists after the controller
0x44
n
There is a local bus interruption after module n
0x45
n
Fault during register communication with module n
9.3.5.3
PROFIBUS DP status messages and arguments
Table 63: PROFIBUS-DP status messages and arguments
Device status
Description
Message
Argument
0x81
0x01
Insufficient parameter data
0x81
0x02
Excessive parameter data
0x82
n
nth parameter byte faulty
0x83
0x01
Insufficient configuration data
0x83
0x02
Excessive configuration data
0x84
n
nth configuration byte (module) faulty
0x85
0x01
Maximum input data length exceeded
0x85
0x02
Maximum output data length exceeded
0x86
0x01
Overflow of the compilation buffer for the DP process map