WAGO I/O System 750
Using in Safety Related Applications 35
750-1505 16DO 24VDC 0.5 A, low-side switching
Manual
Version 1.1.0
Public
Pos: 74.4 /Serie 750 (WAGO I/O SYSTEM)/Einsatz in sicherheitsg erichteten Anwendung en/Hinweise zum Ei nsatz i n Sicherheitsanwendungen @ 6\mod_1258974811438_21.docx @ 44688 @ 2 @ 1
1
Einsatz der rückwir kungsfrei en Digital ausg angskl emme in Sicher heitsanwendungen
7.1
Important Notes
Only operate interference-free I/O modules at a safe extra low voltage!
When using interference-free I/O modules, only use power supplies with
protective extra-low voltage (PELV/SELV) for the 24 VDC power supply.
Note maximum voltage!
Please note that a maximum voltage U
max
only can act on the reaction-free I/O
module in the event of a failure because irreparable damage could occur to the
module otherwise.
For the reaction-free I/O module , the field supply voltage is:
U
max
< 32 V
Note IP54 protection class!
IP54 protection class is absolutely mandatory. This means that the interference-
free digital output module shall only be integrated and operated in switch boxes
or switch cabinets complying with IP54 or higher.
Avoid reverse supply of output!
The 24 V power supply shall never be applied to the output of an interference-
free digital output module. This wiring failure will not be detected by the system.
Avoid reverse supply of module!
A group of interference-free digital output modules shall only be supplied using a
safety switching device. Reverse supply must absolutely be avoided.
Avoid short circuits between outputs!
Short circuits between outputs of different interference-free digital output
modules must absolutely be avoided as they are not detected by the system.
According to EN ISO 13849-2, the following measures are required for an
“external voltage” fault exclusion:
-
Use of cables routed separately and
-
Protection from external damage (e.g., caused by cable duct).