0787-1212
Notes on Operation
Product manual | Version: 1.0.0
35
Compact Power Supply
100%
105%
135%
140%
160%
Constant
Power Mode
24
(VDC)
0
OUT
normal
I
Overload Mode
(105 % up to 135 %)
Constant Power Mode
Short Circuit Protection
(140 % up to 160 %)
Auto Recovery
OUT
U
OUT
(ADC)
I
Figure 22: Output Characteristics
Table 31: Legend for the “Output Characteristics” Figure
Position
Explanation
1
I
OUT(IST)
normal
2
Overload mode (1.05 × I
OUT
< I
OUT(IST)
< 1.35 × I
OUT
); constant power mode
3
Short circuit protection (1.4 × I
OUT
< I
OUT(IST)
); Hiccup mode
7.6 Maintenance
Note
Observe the following for long-term storage:
For long-term storage, power must be applied to equipment with built-in capacitors for
five minutes at least every two years.
The product requires no special maintenance; however it must be protected (as per the
protection class) against dust accumulation, moisture, radiation and aggressive chemi-
cals.
Permitted repairs are limited to the measures listed in these operating instructions.
Should a fault occur nonetheless, return the product to WAGO for repair. Provide the fol-
lowing information:
• Type of fault
• Circumstances (operating conditions, input wiring)
• Your suspicion about the fault’s cause
• Previous instances of unusual incidents etc.