2789-9023
Fieldbus Description
Product manual | Version: 1.0.0
43
EtherNet/IP Communication Module
The following process data can be read out in binary format:
Table 53: Reading Out Process Data in Binary Format
No. Data type
Description
1
UINT16
Module status
Bit 0
Communication with lower-level device OK
2
UINT16
Output voltage (unit: mV)
3
UINT16
Output current (unit: mA)
4
UINT16
Status
Bit 0
DC status OK
Bit 1
Overtemperature
Bit 2
No output voltage
Bit 3
Short circuit at output
Bit 4
Status at digital input
5
UINT16
Warnings
Bit 0
Undervoltage at output
Bit 1
Overvoltage at output
Bit 2
Overload
Bit 3
Configurable overload threshold exceeded
Bit 4
Configurable operating hours reached
Bit 5
TopBoost output
Bit 6
PowerBoost output
Bit 7
Higher device temperature
Bit 8
Digital input active
6
UINT16
Error
Bit 0
Overtemperature, device switched off
Bit 1
No output voltage
Bit 2
Short circuit at output
Bit 3
Circuit breaker tripped
7
UINT16
Control word
Bit 0
Device standby
1
Bit 1
Digital output on
1 Not yet supported by the WAGO Pro 2 Power Supply
The following process data can be written in binary format:
Table 54: Writing Process Data in Binary Format
Byte
No.
Data type
Description
1
UINT16
Control word
Bit 0
Device standby
1
Bit 1
Digital output on
1 Not yet supported by the WAGO Pro 2 Power Supply