2789-9023
Fieldbus Description
Product manual | Version: 1.0.0
35
EtherNet/IP Communication Module
Attribute ID
Access
Data type
Description
Bit 4
Activation of the readout function of the
digital output via the process data
Bit 5
Switching digital output on and off
Bits 6 … 9
Reserved
Bit 10
Inversion
Bits 11 … 15 Reserved
System
Table 35: Parameters – System
Attribute ID
Access
Data type
Description
189
Get/Set
UINT16
Bit 0
1
Behavior when power applied:
Previous state restored
Bit 1
1
Behavior when power applied:
DC output remains switched off
Bit 2
1
Behavior when power applied:
DC output switched on
Bit 3
Switch-on delay enabled
Bits 4 … 5
Reserved
Bit 6
Enable button lock
Bit 7
Lock resetting to factory settings
Bits 8 … 9
Reserved
Bit 10
Inversion
Bits 11 … 15 Reserved
1 These bits are mutually locked.
4.2.7.3 General Services
This object supports the following common services.
Table 36: Common Services
Service
Code
Service Available
Service Name
Description
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
Returns the content of the respective attribute
0x10
No
Yes
Set_Attribute_Single
Modifies an attribute value