4.4 Manual Operation Menu

Manual operation menu

Menu item

Description

Range

Base value

Off = 0/On = 1

Manual on/off via output A1 (solar circulation pump)

0 - 1

0

Activation of manual operation lag time in automatic mode

0 - 600 min

0 min

4.5 Special Functions Menu

Within the first minute after switching on the controller, select the “Special Functions“ menu in order to activate it, so that
the individual parameters can be changed.
After leaving it, the menu remains active for one minute. Afterwards the parameters can only be viewed but not changed.
In order to change the functions again, it is necessary to disconnect the controller from the mains again.

Special functions menu

Menu
item

Application

Description

Range

Base value

0

System choice

0 - 1: Standard single-tank system
0 - 2: Cannot be selected!
0 - 3: SECUSOL system (see SECUSOL instructions for further info)

1 or 3

1

1

System
Protection

Off = 0/On = 1

Activation of system protection.
Cannot be activated with SECUSOL!

0 or 1

1

2

System protection start temperature

115 - 200 °C

135 °C

3

Collector Cooling

Off = 0/On = 1

Activation of collector cooling.
Cannot be activated with SECUSOL!

0 or 1

1

4

Collector cooling start temperature

100 - 150 °C

110 °C

5

Tank Cooling

Off = 0/On = 1

Activation of tank cooling. Only possible with collector cooling.
Cannot be activated with SECUSOL!

0 or 1

0

6

Switch-off temperature

30 - 90 °C

60 °C

7 - 10

Menu items 7-10 are not available for the SUNGO S controller

11

Tube collector
function

Off = 0/On = 1

Activation of vacuum tube collector function

0 or 1

0

12

Run time of solar circulation pump from reaching the switch-on value

1 - 60 s

15 s

13

Switch-on value for temperature increase at sensor T1 (collector)

1.0 - 5.0 K

1.0 K

__

T stop

Only expert personnel

should edit the special functions menu.
Incorrect settings may adversely affect the solar heating
system.

Summary of Contents for SUNGO S

Page 1: ...otection and vacuum tube col lector function Solar charging of 1 tank systems Current reset values 3 temperature inputs Pt1000 1 output speed controlled Contents 1 TechnicalDescription 2 2 GeneralSafety Guidelines 4 2 1 Installer s Qualifications 4 2 2 OperatingRequirements 4 2 3 InstallationandOperatingInformation 4 3 Installation 4 3 1 Installationof theCase 4 3 2 ConnectingWires 5 4 Operation 6...

Page 2: ...omatic operation in the information menu Manual Lag Function In order to check the temperature values in the information menu even when the output channels are set manually a time lag has to be selected in the manual lag function of the manual operation menu After exiting the manual opera tion menu this time span passes once and then is set back to zero In this mode a blinking symbol for the manua...

Page 3: ...f 2 diodes which can be switched anti parallel antiparallel thyristors The thyristors switch through the positive or negative sine half wave as long as a switch on difference exists The triac switch switches off when the temperature falls below the switch off difference System Protection In order to protect system components like solar circulation pump 2 3 way valves etc that are installed in the ...

Page 4: ...stcheckwiththeserviceof Wagner Co The use of the control for non specified operation re sults in a lapse of the guarantee 2 3 Guidelines for Installation and Operation Because Triacs carry 230V current at the case the mains must be disconnected while any installation and wiring work is carried out The mains must be connected to the control via an exter nal ON OFFswitch outside the solar circulatio...

Page 5: ...onnection Mains power is connected from outside the connector via an ON OFF switch If the unit is connected with a plug to a socket the switch can be omitted The unit is designed to work with 230V AC 50Hz Please check that your pump has compatible specifications All earth wires are connected to the PE connectors The neutral terminals N are connected electrically Switch output A1 is a 230 Vnormally...

Page 6: ...enu Information menu Temperature difference Number display for temp or sensor errors Collector temperature Reset symbol Tank temperature lower half Pump ON Pump OFF Output A1 Figure 3 Connections S a f e t y f u s e T1 collector sensor T2 tank sensor lower half T3 tank sensor upper half Mains PE Solar circulation pump PE Mains phase L Mains neutral N Solar circulation pump phase L1 Solar circulati...

Page 7: ... solar Switch off difference T1 T2 solar Minimum temperature source Set point temperature difference speed control solar Solar circulation pump Maximum speed solar circulation pump SECUSOL System filling time SECUSOL dT max __K dT min __K __ C T max __ C T min T start __ d max __ d min __ __K dT Save value Activate save function Decrease value Increase value Ý Ý Ý Activate value Ý ...

Page 8: ...erence between collector and tank is higher than switch on difference solar circulation pump on 1 Sensor T3 tank upper half is simply a measuring sensor therefore it is not monitored by the sensor control 4 3 Settings Menu Settings menu Menu item Description Range Base value Temperature limitation tank lower half 15 90 C 85 C Switch on difference between collector and tank 3 40 K 10 K Switch off d...

Page 9: ... 0 3 SECUSOL system see SECUSOL instructions for further info 1 or 3 1 1 System Protection Off 0 On 1 Activation of system protection Cannot be activated with SECUSOL 0 or 1 1 2 System protection start temperature 115 200 C 135 C 3 Collector Cooling Off 0 On 1 Activation of collector cooling Cannot be activated with SECUSOL 0 or 1 1 4 Collector cooling start temperature 100 150 C 110 C 5 Tank Cool...

Page 10: ...he line or the sensor input on the controller dT too high A fixed value of 20 K is added to the temperature difference between collector T1 and tank sensor T2 The message is displayed if after 30 minutes the total temperature difference has not been reduced Check pump pump connections wiring Check system for air and vent if required Check sensors sensor lines and change sensor if required 4 7 Serv...

Page 11: ...GO S P3 P2 Ta A1 T2 T3 T1 CIRCO T2 ECOplus Ttw T3 P1 T1 BWM Hot water Cold water Oil or gas boiler Heating circuit Collector field T1 Collector sensor T2 Tank sensor lower half T3 Tank sensor upper half P1 Solar circulation pump P2 Heating circuit pump P3 Tank charging pump Ttw Hot water sensor heating control BWM Thermostatic mixing valve ...

Page 12: ...boiler T1 Collector sensor T2 Tank sensor lower half T3 Tank 1 sensor upper half optional P1 Solar circulation pump P2 Heating circuit pump P3 Tank charging pump Ttw Hot water sensor heating control BWM Thermostatic mixing valve Subject to modifications errors excepted Wagner Co 2008 www wagner solar com 12 WAGNER CO Zimmermannstraße 12 D 35091 Cölbe Marburg 49 6421 80 07 0 Fax 80 07 22 ...

Reviews: