Troubleshooting
CoolMatic
54
12
Troubleshooting
The significance of the red LED (fig.
6
2, page 5, fig.
7
2, page 6)
For operational faults it illuminates several times. The number of pulses
depends on the type of fault.
Each flash lasts for one quarter of a second. After the series of impulses a
pause follows. The sequence for the fault is repeated every four seconds.
Number of
flashes
Fault
Possible cause
1
Line Voltage
The supply voltage is outside of the set range.
2
Excessive fan current
The fan load on the electronics unit is more
than 1 A.
3
The motor doesn't start
The rotor is jammed.
The pressure difference in the cooling system
is too high (> 5 bar).
4
Speed too low
If the cooling system is overloaded, the mini-
mum speed of the motor of 1,850 rpm cannot
be maintained.
5
Overheating of the elec-
tronics unit
If the cooling system is loaded too heavily or
the temperature is set too high, the electronics
can overheat.
Constantly
NTC errors
NTC is defective.