What to do, when?
VAS 581 001A
68
The display shows
“Error 30”
Pressure drop during leak
test.
Check device for leaks.
The display shows
“Error 35”
Residual pressure in the air
conditioning system.
Drain and evacuate.
The display shows
“Error 40”
Pressure drop during pres-
sure test.
Check air conditioning sys-
tem and connections for
leaks.
The display shows
“Error 41”
Pressure drop during pres-
sure test.
Check air conditioning sys-
tem and connections for
leaks.
The display shows
“Error 42”
Pressure drop during pres-
sure test.
Check air conditioning sys-
tem and connections for
leaks.
The display shows
“Error 43”
The device was not able to
reduce the pressure suffi-
ciently to begin with the vac-
uum phase.
Check air conditioning sys-
tem and connections for
leaks.
Check pressure sensor cali-
bration.
The display shows
“Error 52”
No USB stick was found/rec-
ognized
Insert the USB stick.
Make sure that USB stick has
been formatted with the
FAT32 file system.
The display shows
“Error 60”
During the hybrid service
(flushing the service hoses
with hybrid oil), a vacuum
could not be achieved.
Are the service hoses con-
nected to the hybrid flush
container?
Is the hybrid flush container
fitted the right way round?
Check the connections for
leaks.
The display shows
“Error 61”
Pressure increase during the
hybrid service (flushing the
service hoses with hybrid oil).
Are the service hoses con-
nected to the hybrid flush
container?
Is the hybrid flush container
fitted the right way round?
Are the service couplings
open?
The display shows
“Error G1”
A connection to the analysis
module could not be made.
Check the connections.
Are the LEDs on the module
activated?
The display shows
“00001”
The readings are unstable.
Keep possible electrical
sources of interference, such
as mobile phones or welding
equipment, away from the
device.
Fault
Cause
Solution