Initial startup
VAS 581 001A
28
7.14
Filling up the internal refrigerant container
I
When the AirConServiceCenter is started for the first time, the internal
refrigerant vessel must be filled from an external refrigerant vessel with at
least 2,000 g of refrigerant.
The unit displays error message 12.
Press
STOP
to confirm.
I
The current supply quantities are displayed in the standby menu.
There are three different types of refrigerant vessel available:
Refrigerant vessels without rising pipe:
These refrigerant bottles have
one
connection.
When filling the AirConServiceCenter, the connection must be on the
bottom (turn the vessel upside down).
Refrigerant vessels with rising pipe:
These refrigerant bottles have
one
connection.
When filling the AirConServiceCenter, the connection must be at the
top (place the vessel upright).
Refrigerant bottles with rising pipe:
These refrigerant bottles have
two
connections. To top up the
AirConServiceCenter, use the connection marked with
L
(= liquid).
When filling the AirConServiceCenter, the connection must be at the
top (place the vessel upright).
1. In the basic menu, use the cursor keys
or
to select
“Other
selections”
:
2. Press
ENTER
to confirm.
3. Use the cursor keys
or to select
“Int. vessel filling”
:
NOTE
The AirConServiceCenter analyzes the purity level of the refrigerant. If
it is below 95 %, the unit does not accept the refrigerant. The contami-
nated mixture must be disposed of externally.
NOTE
Note also the instructions on the refrigerant bottles.
Refrigerant bottles for the R-1234yf refrigerant have a left-hand thread!
Short selection
Free selection
Other selections
ENTER-OK