Important instructions for the connection of consumers
Do not exceed the rated current of all attached consumers
The total rated currents of all connected consumers must not exceed the maxi-
mum rated output current of the inverter.
The maximum rated output current is specified on the nameplate.
Example:
FUE 6/042/200W, maximum rated output current 52 A.
You can connect three IREN 57 with a rated current of 17.3 A each since the
overall current I = 3 x 17.3 A = 51.9 A and is therefore less than 52 A.
However, you cannot connect three IREN 65 with a rated current of 25 A each
since the overall current I = 3 x 25 A = 75 A and therefore exceeds 52 A.
Do not exceed the rated current of the plug receptacle
The rated current of every attached consumer must not exceed the maximum
rated current of the plug receptacle.
The maximum rated current is specified on the plug receptacle.
Example:
FUE 6/042/200W, maximum rated current of a plug receptacle 32 A.
You must not connect consumers whose rated current is higher than 32 A.
WARNING
A damaged machine part or power cable can result in personal injury caused by
electric current.
f
Do not operate a damaged machine!
f
Have a damaged machine repaired immediately.
WARNING
Improper handling can damage the insulation of the inverter.
Mortal danger from electrocution and risk of fire.
f
The total rated current of all connected consumers must not exceed the
maximum rated output current of the inverter.
f
The rated current of every attached consumer must not exceed the maxi-
mum rated current of the plug receptacle.